Burner Adjustment When Connecting Multiple Flues To A Shared Flue System - Viessmann VITODENS 111-W Installation And Service Instructions Manual

Table of Contents

Advertisement

Matching the burner output to the flue system
Correction factor
Flue system
Open flue operation
60 mm
7
Room sealed operation
7
coaxial

Burner adjustment when connecting multiple flues to a shared flue system

When connecting several Vitodens 111-W to a shared
flue system:
Adjust the burner setting of each connected boiler by a
correction factor to match it to the flue system.
System conditions:
Shared flue in shaft
100 mm
7
Balanced flue connection pipe from boiler to shaft,
80/125 mm
7
01. Tap MODE.
02.
/ until CONFI flashes.
03. OK to confirm.
"P" appears in the l.h. display area. The r.h. dis-
play area flashes.
04. Use / to select "12".
05. OK to confirm.
"1" flashes in the l.h. display area.
06. Use / to select "4".
07. OK to confirm.
"0" flashes in the r.h. display area.
08. Refer to the following tables for the correction fac-
tor required for the flue system.
09. Use / to set the correction factor.
10. OK to confirm. The selected value is adopted.
Rated heat-
ing output
(kW)
26
35
60/100 mm
26
35
Commissioning, inspection, maintenance
(cont.)
0
1
2
Max. pipe length (m)
3
12
15
4
9
15
2
6
11
2
5
8
Minimum shaft cross-section
Square: 175 x 175 mm
Round:
195 mm
7
Height between floors min. 2.5 m
Max. 6 boilers with the same rated heating output
connected to the flue system
3
4
5
22
25
16
20
12
16
25
6
25