Service Schedule - Generac Power Systems 0K2502SPFR Owner's Manual

60 hz air-cooled generator
Table of Contents

Advertisement

Available languages

Available languages

Maintenance

Service Schedule

Service
Check Enclosure Louvers
for Dirt and Debris *
Check Lines and Connections for
Fuel or Oil Leaks
Check Engine Oil Level
Check for Water Intrusion **
Check Battery Condition, Electrolyte
Level, and State of Charge
Replace AVR Filter ***
Replace Engine Oil and Oil Filter †
Replace Engine Air Filter
Maintain Spark Plugs
Inspect/Adjust Valve Clearance ‡
Replace Brushes
Contact the nearest Independent Authorized Service Dealer for assistance if necessary.
* Remove any shrubs or tall grasses which have grown within 3 ft. (0.91m) of the intake and discharge louvers on the sides of the enclosure. Clean any debris (dirt,
grass clippings, etc.) which have accumulated inside the enclosure.
** Verify that all sources of potential water intrusion such as water sprinklers, roof run-off, rain gutter down spouts and sump pump discharges are directed away from
the generator enclosure.
*** Replace AVR filter more often if operating in dusty conditions.
† Change engine oil and filter after the first 25 hours of operation. In cold weather conditions (ambient below 40
or if unit is operated continuously in hot weather conditions (ambient above 85
every year or 100 hours of operation.
‡ Check/adjust valve clearance after the first 25 hours of operation.
NOTE: Contact an Independent Authorized Service Dealer or visit
replacement parts.
22
Table 4-1. Service Maintenance Schedule
Daily If Running
Continuously
or
Before Each Use
Schedule A
Every
Every Two
Years
Year
or 200 Hours
º
F / 4.4
º
º
F / 29.4
C), change engine oil and filter
www.generac.com
Owner's Manual for 60 Hz Synergy Generator™
Schedule B
Every Four
Every 1000
Years
or 400 Hours
º
C),
for additional information on
hours