Ups Setup; Inspecting The Equipment; Floor Loading; Clearances - Eaton 9355 Installation And Operation Manual

20/30 kva
Hide thumbs Also See for 9355:
Table of Contents

Advertisement

Chapter 3

UPS Setup

This chapter describes:
Equipment inspection
l
Floor loading and clearances
l
Removing and replacing the cabinet doors
l
Unloading the cabinet(s)
l
The instructions are intended for the chief operator/system supervisor, electrical consultants, and installation
electricians. Local regulations and electrical code must be followed during the UPS installation.

Inspecting the Equipment

If any equipment has been damaged during shipment, keep the shipping and packing materials for the carrier
or place of purchase and file a claim for shipping damage. If you discover damage after acceptance, file a claim
for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with the carrier within 15 days of receipt of
the equipment; 2) Send a copy of the damage claim within 15 days to your service representative.
Note:

Floor Loading

When planning the installation, consider the UPS weight for floor loading. The strength of the installation
surface must be adequate for point and distributed loadings. The approximate weights are shown in the
following table.
Options Cabinet with
Single Transformer
Options Cabinet with
Dual Transformer
Options Cabinet with MBS only

Clearances

The following clearances are recommended for the Eaton 9355 UPS:
From Front of Cabinet
From Back of Cabinet
From Right of Cabinet
Check the battery recharge date on the packaging label. If the date has expired and the batteries were
never recharged, do not use the UPS. Contact your service representative.
Standard Model Floor Loadings
Eaton 9355
20 kVA UPS
30 kVA UPS
EBC 36
EBC 72
36" (91.4 cm) working space
6" (15.2 cm)
Refer to local codes for right side service access [minimum 36" (91.4 cm)]
Eaton 9355 UPS (20/30kVA) Installation and Operation Manual 164201626—Rev F
Maximum Weight
1160 lb (526 kg)
1160 lb (526 kg)
1160 lb (526 kg)
2060 lb (934 kg)
535 lb (243 kg)
792 lb (360 kg)
205 lb (93 kg)
Point Loading
290 lb/in
(20 kg/cm
)
2
2
290 lb/in
2
(20 kg/cm
2
)
290 lb/in
(20 kg/cm
)
2
2
515 lb/in
(36 kg/cm
)
2
2
134 lb/in
2
(9.4 kg/cm
2
)
198 lb/in
(13.9 kg/cm
)
2
2
51 lb/in
2
(3.6 kg/cm
2
)
www.eaton.com/powerquality
9

Hide quick links:

Advertisement