Installation Setup; Equipment Clearances; Location Requirements; Ups Setup - Eaton 9PXM User Manual

Ups 4–20 kva
Hide thumbs Also See for 9PXM:
Table of Contents

Advertisement

Chapter 2

Installation Setup

This chapter explains how to set up and install the Eaton 9PXM eight and twelve-slot cabinets:

Equipment Clearances

l

Location Requirements

l

UPS Setup

l
Anchor Bracket Installation
l
Rack-mount installation
l
Equipment Clearances
All cabinet sizes require the following clearances to allow for servicing and adequate ventilation:
Sides: 15.2 cm (6")
l
Top and back: 30.5 cm (12")
l
Front: 91.5 cm (36")
l
If flexible conduit connects the UPS to the service input and load distribution panels, you may be able to gain
access for servicing by moving the UPS. If this is the case, you must still leave 30.5 cm (12") clearance at the
back and 15.2 cm (6") at the sides of the UPS for ventilation.
External battery cabinets may be installed with bases tight against the UPS cabinet base and against each other.
Location Requirements
Install the Eaton 9PXM UPS as close as possible to the equipment or the load distribution panel it will protect.
If a separate external battery cabinet (EBM) is installed, the battery cabinets must be adjacent to the
Eaton 9PXM UPS. If the batteries will be farther from the cabinet than the standard cables allow, contact your
service representative or your local distributor for assistance.
UPS cabinet dimensions are located in Chapter 10, "Weights and Dimensions" on page 89.
UPS Setup
The Eaton 9PXM UPS eight and twelve-slot cabinets are shipped on a shipping pallet. Power modules and
battery packs are shipped in separate boxes on another pallet.

Eight- and Twelve-Slot Cabinets

Do NOT or attempt to move the cabinet with the power modules or battery packs installed.
NOTE
Do not block the ventilation holes on each side and the back of the cabinet.
NOTE
Installation for the eight-slot cabinets are identical to the twelve-slot cabinets.
Twelve-slot cabinets are shown in these set up instructions.
CAUTION
Eaton 9PXM UPS (4-20 kVA) User's Guide
P-164000669—Rev 05
9