The context menu of WEBcmic is opened:
·
Change the language if needed and open the context menu again
·
After that click on Set Ethernet IP Address
The window for the address assignment is opened.
Click Discover CMICs to find the physically connected automation units within the network.
The found devices -unambigously identified by the respective MAC address – are listed in the
table.
Note
The IP settings depend on the configuration and the used transmission media of your network. For the
setting of these values please contact your network administrator.
Note
With the firmware CPC80 as of revision09 the setting of an IP address by means of WEBcmic is supported
only as long as the default IP address (172.16.0.3) exists in the target device.
SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016
Preparing the Engineering
85