COMBUSTION HEAD ADJUSTMENT

Loosen the screw (A), move the elbow (B) so that
the rear plate of the coupling (C) coincides with the
set point.
Tighten the screw (A).
Example:
The burner is installed in a 40 kW boiler.
Considering efficiency of 90% the burner must
supply around 44 kW.
The diagram shows that for this
output the adjustment must be
made on notch 3.
The diagram is to be used only
for initial settings, to improve air
pressure
switch
operation
improve combustion, it may be
necessary to reduce this setting
(set point toward position 0).
Parts Available from
www.sparesgiant.com

AIR DAMPER ADJUSTMENT

The air damper opening motor (1) controls the damper
(6); the burner does not start until the damper (6) is com-
pletely open.
To adjust the fixed damper (4) it is necessary to:
loosen the screws (3 and 5) and rotate the damper as
far as the required point (2).
Once optimum adjustment has been reached, fix the
screws (3 and 5).
The adjustment of the damper varies in each single appli-
cation, so it is necessary to use a calibration tool to obtain
an efficient combustion result.
Important:
It is advisable to carry out an analysis of the combustion
values with the hood assembled.
3288
kcal/h
kW
60,000
70
60
50,000
or
50
40,000
44
40
30,000
30
20,000
20
10,000
10
0
6
GB
C
A
B
1
2
2
3
D7305
S7015
D5137
3
4
5
Set point
1
5
6
4

Advertisement

Table of Contents
loading

Table of Contents