Electrode positioning

To verify the correct position of the ignition electrode (Fig. 14), you
need to separate the combustion head from the rest of the burner.
Proceed as follows:
 loosen the 4 screws 3)(Fig. 12) and remove the cover 1);
 remove the screws 2) from the two sliding bars 5);
 install the extensions 15) and re-screw the screws 2);
 remove the two screws 4).
 Pull back the burner on the sliding bars 5) of about 4";
 disconnect the electrode lead, then unthread the burner com-
pletely from the sliding bars;
 remove the screw 1)(Fig. 13) and extract the inner part 2) of
the head.
 Check the correct position of ignition electrode, as shown in
Fig. 14.
 Re-install all components with reverse procedure.
Measures must be respected.
WARNING
4.9

Combustion head adjustment

Installation operations are now at the stage where the blast tube
and sleeve are secured to the boiler as shown in Fig. 15.
It is now a very simple matter to set up the combustion head, as this
depends solely on the maximum output developed by the burner.
It is therefore essential to establish this value before proceeding to
set up the combustion head.
There are two adjustments to make on the head:
outside air R1
central air R2
Installation
1
2
D11020
OUTSIDE AIR
ADJUSTMENT (R1)
D1707
19
GB
D10444
Fig. 13
1 / 8 "
1 / 2 0 "
Fig. 14
CENTRAL AIR
ADJUSTMENT (R2)
Fig. 15
20094580