Combustion head adjustment

Rotate the screw 1) until the notch you have found corresponds
with the front surface of the screw itself.
The combustion head is opened by turning the screw 1) anti-
clockwise.
The combustion head is closed by turning the screw 1) clockwise
(Fig. 18)
The burner leaves the factory with the combustion
head set at notch 0 (Fig. 18).
This setting allows to secure the movable compo-
WARNING
nents during the transport of the burner.
Before starting up the burner, carry out the settings according to
the required output and indicated in the diagram (Fig. 19).
NOTE:
Depending on the specific application, the adjustment can
be modified.
No. Notches (air = gas)
Max burner output (kW)
Installation
20081480
20073539
Only for the RS 310 FGR model:
The RS 310 FGR burner is equipped with central air/gas adjust-
ment. The factory setting is the following:
AIR = notch 9
GAS = notch 0.
Do not change these settings!
WARNING
Only for specific cases, to change the central gas setting, do as
follows:
 loosen the screws 1) and rotate the ring nut 3) until the notch
you have found corresponds with the indicator 4)(Fig. 20).
To change the central air setting, do as follows:
 loosen the screws 1) and rotate the ring nut 2) until the notch
Fig. 18
you have found corresponds with the screw 1);
 Block the 2 screws 1)(Fig. 20).
20084828
23
GB
Fig. 19
Fig. 20
20155699