Electrical Ratings Indoor Unit - York KES180 Installation Instruction

Split system coolinh only indoor unit
Table of Contents

Advertisement

550.13-N10Y
TABLE 9: ELECTRICAL RATINGS INDOOR UNIT
B
N
LOWER
OMINAL
M
HP
H
KW
OTOR
EATER
10 KW
20 KW
3
30 KW
50 KW
20 KW
30 KW
5
40 KW
50 KW
1.
Maximum fuse or maximum circuit breaker (HACR type per NEC).
2.
Based on three, 75 C insulated copper conductors in conduit and ambient of 30 C.
3.
Based on a 5% voltage drop, since unit controls are powered off the unit supply. Two minute time delay between system 1 and
system 2.
15
M
INIMUM
P
H
OWER
EATER
C
IRCUIT
S
FLA
UPPLY
A
MPACITY
K1ES180A33
208-3-60
20.8
35.5
230-3-60
23.1
38.1
460-3-60
11.5
19.0
208-3-60
41.6
61.5
230-3-60
46.2
66.9
460-3-60
23.1
33.5
208-3-60
62.5
87.6
230-3-60
69.3
95.8
460-3-60
34.6
47.8
208-3-60
104.4
140.0
230-3-60
115.2
153.2
460-3-60
57.6
76.6
L1ES240A33
208-3-60
41.6
68.0
230-3-60
46.2
70.6
460-3-60
23.1
35.3
208-3-60
62.5
94.1
230-3-60
69.3
99.4
460-3-60
34.6
49.7
208-3-60
83.3
120.1
230-3-60
92.1
127.9
460-3-60
46.1
64.0
208-3-60
104.4
146.5
230-3-60
115.2
156.8
460-3-60
57.6
78.4
M
INIMUM
M
AXIMUM
W
S
IRE
IZE
1
F
S
USE
IZE
2
AWG
40
8 AWG
40
8 AWG
20
14 AWG
70
6 AWG
70
4 AWG
35
10 AWG
90
3 AWG
100
3 AWG
50
8 AWG
150
0 AWG
175
2/0 AWG
80
4 AWG
70
4 AWG
80
4 AWG
40
8 AWG
100
3 AWG
100
3 AWG
50
8 AWG
125
1 AWG
150
1 AWG
70
6 AWG
150
0 AWG
175
2/0 AWG
80
4 AWG
M
AXIMUM
M
INIMUM
W
L
IRE
ENGTH
D
ISCONNECT
3
A
MPS
FEET
140
60
133
60
132
30
222
60
337
100
335
60
446
100
423
100
533
60
895
150
1073
150
1347
100
186
100
251
100
381
60
233
100
315
100
381
60
371
150
501
150
604
100
469
150
798
150
962
100
Unitary Products Group
®