the Bell Cutoff time expires (Section [005] "System Times"), or
until a code is entered (see Section 5.13 "Bell" on page 22).
NOTE: If a second Fire type zone is violated or if the Fire keys
are pressed during the delay period, the panel will latch the
alarm output and will immediately communicate the alarm.
A violated Fire zone will be displayed on all keypads and can
be delayed at any keypad. Typically this zone is used for
latching smoke detectors.
[08] Standard 24 Hour Fire Zone
NOTE: Do not wire Fire zones on keypad zone terminals if the
DEOL supervision option is enabled for the panel (section
[013], option [2]).
When this zone is violated, the panel will immediately latch the
alarm output and communicate to the central station. The
alarm will sound until the Bell Cutoff time expires, or until a
code is entered (see section 5.13 "Bell" on page 22).
A violated Fire zone will be displayed on all keypads. Typically
this zone is used for pull stations.
[09] 24 Hour Supervisory Zone
If this zone is violated when the system is either armed or dis-
armed, the panel will report to the central station, and will log
the zone alarm to the Event Buffer. This zone gives a silent
alarm by default.
NOTE: Do not wire 24-Hour Supervisory zones on keypad
zone terminals.
[10] 24 Hour Supervisory Buzzer Zone
If this zone is violated when the system is either armed or dis-
armed, the panel will immediately latch the keypad buzzer
until a valid access code is entered and will immediately com-
municate to the central station.
[11] 24 Hour Burglary Zone
If this zone is violated when the system is either armed or dis-
armed, the panel will immediately latch the alarm output and
communicate to the central station. The alarm will sound until
the Bell Cutoff time expires, or until a code is entered (see
section 5.13 "Bell" on page 22).
[12] - [20]
The following zone definitions operate similar to the 24 Hour
Burglary except for the System Event output type and the SIA
identifier:
[12] 24 Hour Holdup Zone - This zone gives a silent alarm by
default.
[13] 24 Hour Gas Zone
[14] 24 Hour Heat Zone
[15] 24 Hour Medical Zone
[16] 24 Hour Panic Zone
[17] 24 Hour Non-Medical Emergency Zone
[18] 24 Hour Sprinkler Zone
[19] 24 Hour Water Flow Zone
[20] 24 Hour Freezer Zone
[21] 24 Hour Latching Tamper
If this zone is violated, the installer must enter Installer's Pro-
gramming before the system can be armed.
NOTE: Wireless zones should not be programmed as zone
types [22] - [24].
[22] Momentary Keyswitch Arm Zone
Momentary violation of this zone will alternately arm/disarm
the system. Tampers and faults will not arm/disarm the sys-
tem, but only activate the appropriate trouble.
[23] Maintained Keyswitch Arm Zone
When this zone is violated, the system will arm. When this
zone is secured, the system will disarm. Tampers and faults
will not arm/disarm the system, but only activate the appropri-
ate trouble.
[24] For future use
[25] Interior Delay Zone
This zone type is normally used with motion detectors and has
a standard exit delay time.
If the panel is Away armed (a delay zone is violated during the
exit delay, or the Away function key is used), the Interior Delay
zone will work the same as the Interior zone [04].
If the panel is Stay armed (a delay zone is NOT violated dur-
ing the exit delay, the Stay key is used, or [*][9] is used for
arming), a violation of the zone will initiate Entry Delay 1.
[27] Push to Set Zone
If any zones are programmed as Push to Set, when the system
is armed, the panel will suppress all audible exit delay beeps/
squawks and begin an infinite silent exit delay. When a user
violates and restores a Push to Set zone, the panel will wait 5
seconds, then terminate the Exit Delay and arm the system.
NOTE: Do not enable Exit Delay Termination if this zone type
is used (see 5.18 "Entry/Exit Delay Options" on page 24). Do
not change the attributes of Push to Set zones from the default
settings.
[28] 24 Hour Bell/Buzzer Zone
This zone works like a 24-Hour Burglary zone (zone type [11])
while armed, and a 24-Hour Supervisory Buzzer zone (zone
type [10]) while disarmed. When the panel is armed and this
zone is violated, the bell sounds until the bell time-out timer
expires. When the panel is disarmed and this zone is violated,
the keypad buzzers sound until a user enters an access code.
[87] Delayed 24 Hour Fire (Wireless)
This zone type operates the same as [07] Delayed 24 Hour
Fire Zone and must be used if the smoke detector is wireless.
[88] Standard 24 Hour Fire (Wireless)
This zone type operates the same as [08] Standard 24 Hour
Fire Zone and must be used if the smoke detector is wireless.
Zone Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [001]
Zone Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [202]
5.3

Zone Attributes

NOTE: All zones, with the exception of 24 Hour and Fire, will
provide an exit delay.
NOTE: Do not change the attributes for Fire Zones from the
default settings.
Additional zone attributes can be programmed to customize
the operation of a zone for a specific application. The follow-
ing attributes are programmable for each zone:
Audible / Silent – This attribute determines whether or
not the zone will activate the alarm output.
Pulsed / Steady – This attribute determines whether the
alarm output will be steady or will pulse on and off every
second.
Activate Chime – This attribute determines whether or
not the zone will activate the chime feature (see "[*][4]
Door Chime On/Off" on page 9).
Bypass Enable – This attribute determines whether or
not the zone can be manually bypassed (see "[*][1]
Bypassing and Activating Stay/Away Zones" on page 7).