Troubleshooting
: The compressor discharge temperature sensor breakaway
Outdoor unit display
Indoor unit display
Judgment method
Causes
1. Judge method
1) Cooling operation
Tcond, out - Tair, out > 3˚C
Tair, in - Teva, in > 4˚C
Tair, in - Teva, out > 4˚C
Compressor running &
indoor unit on and thermo on
Error contents
2) Heating operation
High pressure average > 15kg/cm
Low pressure average < 5kg/cm
Teva, out - Tair, in ≥ 3˚C
Teva, in - Tair, in ≥ 2˚C
Tcond, out - Tair, out < 2˚C
Compressor running &
indoor unit on and thermo on
Error contents
12-70
(Operation)
(Timer)
- Refer to the below judge method
- Loading failure of digital compressor or OLP Trip
2
2
(Fan)
(Filter)
(Removing frost)
NO
NO
NO
OK
Loading failure or OLP Trip
NO
NO
NO
NO
NO
OK
Loading failure or OLP Trip