Safewatch Pro 3000 Installation Instructions
1. The 4285/4286 Phone module and 7720PLUS or 7820 Long Range Radios have
not been UL tested and cannot, therefore, be used in a UL installation.
2. Entry Delay No. 1 (field 35) cannot be greater than 20 seconds, and Entry Delay
No. 2 (field 36) cannot be greater than 20 seconds for UL installations.
3. The maximum number of reports per armed period (field 93) must be set to "0"
(unlimited) for UL installations.
4. Periodic testing (see scheduling mode) must be at least every 24 hours.
5. Alarm Sounder plus Auxiliary Power currents must not exceed 700mA total for
UL installations (Aux power 600mA max.).
6. Downloading is not permissible for UL installations.
The California State Fire Marshal and UL have regulations which require that all residential fire alarm control
panels must be provided with a backup battery which has sufficient capacity to operate the panel and its attached
peripheral devices for 24 hours in the intended standby condition, followed by at least 4 minutes in the intended
fire alarm signaling condition. This control panel can meet these requirements without using a supplementary
power supply, provided that the panel's auxiliary power and bell output currents are limited as indicated below.
Output Current Total
700mA maximum total of
auxiliary power plus bell
output currents
‡ NOTE: Use two batteries, connected in parallel. Obtain an Ademco Battery Harness Kit SA5140-1. (Both batteries
will fit inside the panel's cabinet.)
15-2
CALIFORNIA STATE FIRE MARSHALL (CSFM) AND UL RESIDENTIAL FIRE
24-HOUR BATTERY BACKUP REQUIREMENTS
OUTPUT LIMITATIONS TO MEET CSFM 24 HOUR BATTERY BACKUP REQUIREMENTS
AND UL RESIDENTIAL FIRE INSTALLATIONS
OUTPUT CURRENT LIMITATIONS
Maximum Auxiliary Current
160mA
200mA
425mA
500mA
UL NOTICES
Battery Capacity
To Use (Amp/Hrs)
45mA
17.2AH
BATTERY INFORMATION
Recommended Battery
(Yuasa Model No.)
4AH
NP4-12
7AH
NP7-12
8AH
NP4-12 (two) ‡
14AH
NP4-12 (two) ‡
NPG18-12