Notices

Notices

Power

2
Juniper Networks G10 CMTS Pre-Installation Guide
This equipment is intended only for installation in a
restricted access location within a building.
This equipment is intended for indoor use only.
This equipment does not have a direct copper
connection to the outside plant.
Removal of power supplies or cards will result in
access to hazardous energy.
Each power cord must be connected to an
independent branch circuit.
This is a Class A product. In a domestic environment this
product may cause radio interference in which case the
user may be required to take adequate measures.
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) this device must accept any interference received,
including interference that may cause undesired operation.
The G10 CMTS can be configured with either AC or DC power supply modules. To support a
fully-populated CMTS, the installation site must be able to source 1700 watts of input power.
Fully populated, the CMTS is configured with 10 power supplies.
The G10 CMTS chassis midplane is electrically partitioned
into A and B domains. To support redundancy, each
domain must be sourced by separate power supplies and
circuit protection measures.
Ensure that all power distribution panel switches on the
rear of the CMTS are in the OFF position prior to
connecting any electrical power cords. Also ensure that the
CMTS chassis is properly grounded to earth prior to
connecting any source of power.