Further Details Regarding The Individual Steps - Viessmann VITOCROSSAL 200 Service Instructions Manual

Type cm2 gas condensing boiler with matrix radiant burner
Hide thumbs Also See for VITOCROSSAL 200:
Table of Contents

Advertisement

Further details regarding the individual steps

Checking the high limit safety cut-out setting
Never set the high limit safety cut-out
higher than 110 °C, set it to a maximum
of 110 °C if required.
Filling the heating system with water and venting the system
Record the fill volume, water hardness
and pH value on page 29 and 30.
Filling the siphon with water
Commissioning the system
Control unit operating and serv-
ice instructions, and neutralising
system operating instructions
Commissioning, inspection, maintenance
Control unit installation and serv-
ice instructions
Note
Observe the "Water quality require-
ments" on page 62.
1. Undo the siphon and fill with water
(otherwise flue gas may escape).
2. Check that the condensate can drain
freely.
3. Refit the siphon.
1. Check the heating system pressure.
Permissible boiler operating pres-
sure: 4 bar
7