Commissioning, inspection, maintenance
Further details regarding the individual steps
Checking the burner gauze assembly
Installation instructions
Replacing burner components
Checking the ignition electrodes and ionisation electrode
Ignition electrodes
3.5
24
+
0.5
-
1. Undo fitting A on the gas supply
pipe.
2. Undo the screws on the boiler door
and open the door.
3. Check the wire mesh of burner gauze
assembly B and thermal protection
ring C for damage. Slight wavy
deformations of burner gauze
assembly B are OK.
4. Replace burner gauze assembly B
and thermal protection ring C if
required.
Ionisation electrode
Check the ignition electrodes and the
ionisation electrode for correct gap
towards the burner gauze assembly and
damage (replace if required).
(cont.)