Agent release control system six-zone releasing fire control panel
Hide thumbs Also See for MRP-2002:
Table of Contents

Advertisement

Circuit Mapping and Cross-Zoning
Example 4: A dual hazard, cross-zoned application using four input zones and two releasing output
circuits. Input Zones 1 and 2 are cross-zoned to activate Output Circuit 2, which is programmed as
RELEASE 1. Input Zones 3 and 4 are cross-zoned to activate Output Circuit 3, which is
programmed as a RELEASE 2.
Output Circuit 1 is programmed as alarm NAC using the OUTPUT CIRCUITS menus.
Output Circuit 2 is programmed as Release Circuit 1 using the OUTPUT CIRCUITS menus.
Output Circuit 3 is programmed as Release Circuit 2 using the OUTPUT CIRCUITS menus
Output Circuit 4 is programmed as supervisory NAC using the OUTPUT CIRCUITS menus.
Any of smoke detector Input Zones 1 through 4 will directly activate Output Circuit 1 (Alarm
NAC) but not Output Circuits 2, 3 or 4.
Smoke detector Input Zones 1 and 2 are cross-zoned (both must be in alarm) to activate Output
Circuit 2 (Release 1) but not Output Circuits 3 or 4.
Smoke detector Input Zones 3 and 4 are cross-zoned (both must be in alarm) to activate Output
Circuit 3 (Release 2) but not Output Circuits 2 or 4.
1=WATERFLOW NS
2=COMBO
3=COMBO W/AR. SUPERV
1=WATERFLOW NS
2=COMBO
3=COMBO W/AR. SUPERV
OUTPUT MAP ZONE 1
1=ALARM NAC
2=RELEASE 1
3=RELEASE 2
1=SUPV BELL NAC
1=ALARM NAC
2=RELEASE 1
3=RELEASE 2
1=SUPV BELL NAC
REL 1 CROSS GROUP 1
1=ZONE 1
2=ZONE 2
3=ZONE 3
98
ZONE 1 TYPE
ZONE 2 TYPE
YES
YES
NO
OUTPUT MAP ZONE 1
N/A
OUTPUT MAP ZONE 3
YES
NO
YES
OUTPUT MAP ZONE 3
N/A
YES
YES
NO
Input-to-Output Circuit Mapping and Cross-Zone Operation
ZONE 3 TYPE
1=WATERFLOW NS
2=COMBO
3=COMBO W/AR. SUPERV
ZONE 4 TYPE
1=WATERFLOW NS
2=COMBO
3=COMBO W/AR. SUPERV
OUTPUT MAP ZONE 2
1=ALARM NAC
2=RELEASE 1
3=RELEASE 2
OUTPUT MAP ZONE 2
1=SUPV BELL NAC
OUTPUT MAP ZONE 4
1=ALARM NAC
2=RELEASE 1
3=RELEASE 2
OUTPUT MAP ZONE 4
1=SUPV BELL NAC
REL 2 CROSS GROUP 1
1=ZONE 1
2=ZONE 2
3=ZONE 3
REL 2 CROSS GROUP 1
1=ZONE 4
2=ZONE 5
3=ZONE 6
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016