FACP Configuration Templates
Device Installation Example for Template 10
Output
Output
Circuit #2
Circuit #1
Release
Release
Solenoid 1
Solenoid 2
B
B
B
B
-
-
+
+
1 1
2 2
+
-
+
-
TB4
TB5
OUT1
OUT2
Notes:
1.
All End-of-Line Resistors, illustrated in this example, are 4.7KΩ, ½ watt (PN: 71252).
2.
All devices are connected as Class B circuits. For details on connecting as Class A circuits,
refer to "CAC-5X Class A Converter Module" on page 31.
130
Input Circuit #1
2-Wire Smoke
Input Circuit #2
2-Wire Smoke
Input Circuit #3
Manual Release/Abort Sw. Combo
Input Circuit #4
2-Wire Smoke
Input Circuit #5
2-Wire Smoke
B
B
B
B
B
B
B
B
B
-
-
-
-
-
+
+
+
+
2 2
3 3
4 4
1 1
5
+ - + - + - + - + -
Template 10: Dual Hazard - Single Detector
Output
Circuit #3
Release
Stage
Coded
+
+
+
B
B
-
+
3 3
+
-
TB7
OUT3
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016
Output
Circuit #4
Release
Stage
Coded
+
Input Circuit
#6
Manual
Release/Abort
+
Sw. Combo
+
B
B
B
B
-
-
+
+
4 4
6 6
+
-
+ -
TB6
OUT4