Diagnosis
box 23
Replace the servomotor of the internal 3-way valve, see box 190.
step 30
Check the power supply cable of the internal 3-way valve, see box 191.
step 31
Is the power supply cable of the internal 3-way valve in good condition?
step 32
Replace the cable loom (or the affected part thereof).
step 33
Check the movement of the servomotor of the Buderus 24V AC external 3-way valve, see box 211.
step 34
Does the servomotor of the Buderus 24V AC external 3-way valve operate correctly?
step 35
Check to ensure that the the Buderus 24V AC external 3-way valve has been fitted correctly,
step 36
see box 227.
Has the Buderus 24V AC external 3-way valve been fitted correctly?
step 37
Install the Buderus 24V AC external 3-way valve correctly, see box 227.
step 38
Check to ensure that the Buderus 24V AC external 3-way valve is actuated correctly,
step 39
see box 212 and box 228.
Does the Buderus 24V AC external 3-way valve actuate correctly?
step 40
Replace the servomotor of the Buderus 24V AC external 3-way valve, see box 217.
step 41
Check the wiring of the Buderus 24V AC external 3-way valve, see box 220.
step 42
Is the wiring of the Buderus 24V AC external 3-way valve in correct condition?
step 43
Replace the wiring of the Buderus 24V AC external 3-way valve.
step 44
Check the drive mechanism of the Buderus 24V AC external 3-way valve, see box 221.
step 45
Is the drive mechanism of the Buderus 24V AC external 3-way valve working correctly?
step 46
Replace the internal components of the Buderus 24V AC external 3-way valve, see box 224.
step 47
Check the wiring of the Buderus 24V AC external 3-way valve between the connection box or moving plug-
step 48
and-socket connection and the DBA control panel as per box 287.
box 24
On combi boiler supply: hot water available, but no heating operation.
On system boiler supply: no heating operation.
Hot water may be available, but no heating operation.
Check to ensure that the power supply cable to the RTH converter/Junction box has been installed correctly,
step 1
see box 285.
Is the 230V connection to the RTH converter/Junction box fitted correctly?
step 2
Correctly attach the switch live to terminal 1 and Neutral to terminal 2 on the 230V connector, see box 285.
step 3
Disconnect black leads from terminals 1 & 2 on the back of the DBA and test for continuity between the two
step 4
leads.
No continuity check S/L and N connections are made correctly and that there is 230v between the two.
Replace RTH converter/Junction box.
Continuity reconnect the cables to terminals 1 & 2 and check the connections between the terminals and
the DBA.
Is the volt free connection to the RTH converter/Junction box fitted correctly?
step 5
Check to ensure that the connections of the external control unit are attached to terminal 1 and 2 of the
step 6
connection block, indicated by a clock inside a rectangle, see box 286 and box 285 (item 3).
We reserve the right to make technical modifications
26
Servicing manual Gas condensing boiler Buderus 500-24/S, 500-24/C and 500-28/C • Issued 02/2006
Yes:
No:
Yes:
No:
Yes:
No:
Yes:
No:
Yes:
No:
Yes:
No:
Yes:
No:
Yes:
No:
Buderus Ltd. • http://www.buderus-domestic.co.uk
box 42
box 41
step 33
box 42
step 36
step 39
step 45
step 38
box 42
step 41
step 42
box 42
step 47
step 44
box 42
box 41
step 47
box 42
step 4
step 3
box 42
step 6
step 8