INSTALLATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST MODELS: WFERV-A-X WFERV-A-4 Bard Manufacturing Company, Inc. Manual: 2100-495A Supersedes: 2100-495 Bryan, Ohio 43506 File: Volume III, Tab 19 Since 1914...Moving ahead, just as planned. Date: 04-02-08 Manual 2100-495A Page 1 of 21...
It is designed as a single package, which can be easily factory or field installed for new installations or retrofit to Bard WF wall mounted units. The package consists of a UNPACKING unique rotary Energy Recovery Cassette that can be easily Upon receipt of the equipment, be sure to compare the removed for cleaning or maintenance.
BASIC INSTALLATION (Field Installation) drainage of any water entering damper assembly. 1. Unpack the ventilator assembly, which includes the 7. Remove cassette and plug in exhaust blower. integral ventilator with attached electrical harness Replace cassette. (See Figure 6.) and miscellaneous hardware. 8.
16. Disconnect the wires connected in Step 10 if other 18. Close front door. control options are to be used. 19. Apply Certification label, included with Installation 17. Replace the lower service access panel with the Instructions, next to unit Serial Plate. new panel provided.
FIGURE 2 REMOVE VENT OPTION DOOR FRONT DOOR VENT OPTION EXHAUST DOOR COVER PLATES MIS-2350 FIGURE 2A ASSEMBLY OF EXHAUST BLOWER ENCLOSURE PART NUMBERS COLOR BEIGE 134-248-X 134-244-X 134-243-X GRAY 134-248-4 134-244-4 134-243-4 MIS-2461 Manual 2100-495A Page 7 of 21...
FIGURE 3 FILTER AND EXHAUST PLATE LOCATION FRONT DOOR REAR EXHAUST FILL PLATE FRONT EXHAUST FILL PLATE FILTER SCREW MIS-2345 Manual 2100-495A Page 8 of 21...
FIGURE 4 INSTALLATION OF EXHAUST BLOWER ASSEMBLY FASTEN ASSEMBLY TO CONDENSER PARTITION WITH (4) SCREWS DO NOT REMOVE FRONT PLATE LOWER WFERV ASSEMBLY LOCATING HOLES RIGHT SIDE ATTATCH EXHAUST BLOWER ENCLOSER WITH SCREWS PROVIDED AS SHOWN. MIS-2353 Manual 2100-495A Page 9 of 21...
FIGURE 7 WIRING – 230 VOLT 230 VOLT WIRES INSERTED WITH BLOWER WIRES, CONNECT WIRES TO "L1" AND "L2" ON CONTROL BOARD AS SHOWN ON WIRING DIAGRAM GROUND WIRE CONNECT LOW VOLTAGE WIRES TO "C", "W1", AND "G" AS SHOWN ON WIRING DIAGRAM MIS-2356 Manual 2100-495A...
When designing the control circuit for structure. Bard markets the CS2000 for this use. the ventilator, the following requirements must be met. 3. Use a DDC control system to control the WFERV...
Proper cleaning of the Bard energy recovery wheel will maintenance of system performance and air quality. The restore latent effectiveness to near original performance.
Page 17
QUARTERLY MAINTENANCE NOTE: Discoloration and staining of the wheel does not affect its performance. Only 1. Inspect mist eliminator/prefilter and clean if excessive buildup of foreign material needs necessary. This filter is located in the fresh air to be removed. intake hood on the front of the unit.