3. Mini VRF System Alarm Codes
P03 Compressor Discharge Temperature Error
1.
Error Detection Method
When the discharge temperature is over 106°C.
2.
Error Diagnosis
1 Adjustment
to
1-1
Not additional refrigerant charged
refrigerant
charge
1-2
Tends to have insufficient refrigerant charge in the system.
2 Blockage in
2-1
Service valve inside the outdoor unit closed
refrigerant
circuit
2-2
Are the tubes clogged?
Is the outdoor unit's electronic control valve operating correctly?
2-3
(Check for debris clogging the electronic control valve, a problem
with the electronical coil and/or the control PC board.)
Is it observable difference in status of the dew or frost between
2-4
the strainer's primary and secondary sides?
5 - 39
Mini VRF SYSTEM
Trouble Diagnosis
Yes
Additional
refrigerant charge
No
2-2
Yes
Adjust the
refrigerant amount
No
Replace CR board
Yes
Open service valve
No
2-2
Yes
Avoid clogging
No
2-3
Yes
2-4
Replace the
No
electronic control
valve
Yes
Replace the strainer
No
Replace CR board
5