Fitting Tank Temperature Sensor (CVBA only)
IMPORTANT
To prevent equipment damage, cables must not come
into contact with hot parts.
Ensure adequate thermal insulation between cables
and hot pipework.
Legend
A Dry sensor well for tank temperature controller
22
Vitosol DHW Solar Pack Installation
H Never wrap insulating tape around the sensor.
H Secure the tank temperature sensor on the outside of
the contact spring of the sensor retainer (not in the
groove) so that it is flush with the front of the spring.
H Insert the sensor retainer together with the sensor into
the dry sensor well A as far as it will go.
IMPORTANT
Temperature sensor for tank temperature control is not
part of the Solar Pack and must be field supplied.
The sensor is typically part of the boiler control system.