Figure 2 Mounting Instructions - Bard HA4S4KA Installation Instructions Manual

Wall-mounted packaged air conditioner
Table of Contents

Advertisement

The unit rating plate lists a "Maximum Time Delay
Relay Fuse" or circuit breaker that is to be used with
the equipment. The correct size must be used for
proper circuit protection and also to assure that there
will be no nuisance tripping due to the momentary
high starting current of the compressor motor.
The disconnect access door on this unit may be
locked to prevent unauthorized access to the
disconnect. To convert for the locking capability,
REQUIRED DIMENSIONS TO MAINTAIN
30 1/2
1/4" MIN. CLEARANCE FROM
COMBUSTIBLE MATERIALS
REQUIRED DIMENSIONS TO MAINTAIN
RECOMMENDED 1" CLEARANCE FROM
COMBUSTIBLE MATERIALS
C
D
Supply Opening
16"
16"
16"
Return Opening
1
16"
1
6
"
2
3"
1
16"
1"
4"
7
2
1
"
Typ.
8
1
6
"
2
Dimension is 21" on 95" tall units.
1
Dimension is 10" on T48H1 & T60H1.
2
Dimension is 6" on T48H1 & T60H1.
3
Wall Opening and Hole Location View
Mounting Instructions
SEAL WITH BEAD
OF CAULKING ALONG
ENTIRE LENGTH OF
A
B
C
D
E
10 1/2 6 1/4
1 1/4
29 3/4
32
12
5 1/2
2
29
A
C
B
E
16"
30"
1
3
"
7
8
"
4"
8
Typ.
1
2
"
3
8
1
6
"
2
bend the tab located in the bottom left hand corner of
the disconnect opening under the disconnect access
panel straight out. This tab will now line up with the
slot in the door. When shut, a padlock may be placed
through the hole in the tab preventing entry.
See Start Up section for information on three phase
scroll compressor start ups.
FIGURE 2
NOTE: It is recommended that a bead of silicone
TOP.
TOP
WALL
HEATER ACCESS
PANEL
Right Side View
caulking be placed behind the side
mounting flanges and under the top
flashing at the time of installation.
RAIN FLASHING
SUPPLIED
FOAM AIR SEAL
WALL STRUCTURE
1/4" CLEARANCE ON ALL
FOUR SIDES OF SUPPLY
AIR DUCT IS REQUIRED
FROM COMBUSTABLE
MATERIALS
SUPPLY AIR
DUCT
RETURN AIR
OPENING
NOTES:
IT IS RECOMMENDED THAT A BEAD OF
SILICONE CAULKING BE PLACED BEHIND
THE SIDE MOUNTING FLANGES AND UNDER
TOP FLASHING AT TIME OF INSTALLATION.
Manual
Page
MIS-416 E
2100-646
9 of 26