For these checks national regulations must be followed. If
the national regulation does not specify any details, refer
to standard EN 378-2 as follows:
External visual installation checks:
Compare the complete installation with the refrigera-
tion system and power circuit diagrams.
Check that all components comply with the design
specifications.
Check that all protection documents and equipment
provided by the manufacturer (dimensional drawings,
P&ID, declarations etc.) to comply with the regulations
are present.
Verify that the environmental safety and protection and
devices and arrangements provided by the manufacturer
to comply with the regulations are in place.
Verify that all documents for pressure containers, certifi-
cates, name plates, files, instruction manuals provided
by the manufacturer to comply with the regulations
are present.

3 - DIMENSIONS, ClEARANCES, WEIgHT DISTRIbUTION

3.1 - 30RW/30RWA 020-045 - unit without hydronic module (standard)

124
1
50
900
30RW/30RWA
legend:
All dimensions are in mm.
Water inlet
Water outlet
A
Condenser (water inlet/outlet for 30RW units)
B
Evaporator
C
Refrigerant inlet/outlet (30RW only)
Clearances required for maintenance
1
Power supply
8
695
30RWA
1
900
Verify the free passage of access and safety routes.
Check that ventilation in the plant room is adequate.
Check that refrigerant detectors are present.
Verify the instructions and directives to prevent the
deliberate removal of refrigerant gases that are harmful
to the environment.
Verify the installation of connections.
Verify the supports and fixing elements (materials,
routing and connection).
Verify the quality of welds and other joints.
Check the protection against mechanical damage.
Check the protection against heat.
Check the protection of moving parts.
Verify the accessibility for maintenance or repair and
to check the piping.
Verify the status of the valves.
Verify the quality of the thermal insulation and of the
vapour barriers.
B
A
30RW
A
b
NOTE: Non-contractual drawings. Refer to the certified
dimensional drawings.
For the positioning of the fixing points, weight distribution
and centre of gravity coordinates, also refer to the certified
drawings.
For 30RWA units without condenser, installed with a
remote air-cooled condenser, the refrigerant inlet and
outlet position correspond to the condenser water inlets
and outlets. See C in the legend on the left.
C
165
368
B
30RWA
30RW 020-030
30RW 040-045
1-1/4" Gas
2" Gas
1-1/4" Gas
2" Gas