40SMC---N

Refrigerant line connection (Flare connnections)

For refrigerant tubes use seamless, insulated refrigeration grade
tube, (Cu DHP type according to ISO1337), degreased and
deoxidized, suitable for operating pressures of at least 4200 kPa
and for burst pressure of at least 20700 kPa.
Under no circumstances must sanitary type copper pipe be used.
N.B.: Gas extra-charge: outdoor unit 38YY060G903, add 450 g.
³
LINES
Liquid
,
Suction
GB - 10
MODEL
Copper tubing
40SMC009N +
40SMC012N +
40SMC018N +
40SMC024N +
40SMC028N +
40SMC036N +
40SMC048N +
40SMC060N +
40SMC009N +
40SMC012N +
40SMC018N +
40SMC024N +
40SMC028N +
40SMC036N +
40SMC048N +
40SMC060N +
Diameter
tubing
mm
(inches)
6,35
(1/4")
9,52
(3/8")
12,70
(1/2")
15,87
(5/8")
19,05
(3/4")
Insufficient tightening torque will cause gas leaks.
Overtightening the fittings will damage the tube flaring and cause
gas leaks.
·
³
Outdoor unit
·
Field installed
»
40SMC---N
Pressure needle nut
3 way valve nut
Flared nut
(Outdoor unit side)
Flared nut
1/4"
1/4"
1/4"
1/4"
1/4"
1/4"
1/4"
1/4"
1/4"
1/4"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
1/2"
1/2"
1/2"
1/2"
5/8"
5/8"
5/8"
5/8"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
Min. thikness Tightening
nominal
torque
mm
Nm
0,760
18
0,812
42
0,812
55
0,890
65
0,890
100
»
Flare connection body
Liquid or suction line
(Supplied by the installer)
Evaporator coupling flare nut
Coupling
1/4"
1/4"
1/4"
1/4"
1/4"
3/8"
3/8"
3/8"
3/8"
1/2"
1/2"
5/8"
5/8"
3/4"
3/4"
3/4"