218
Input Power Connections
Warning! Do not operate the drive outside the nominal input line voltage
range. Over-voltage can result in permanent damage to the drive.
Input Power Specifications
Prospective short-
circuit current
Fundamental power
factor (cos phi
Cable Temperature
Disconnect Device
The ACS550 does not include a disconnect device. A means to disconnect input
power must be installed between the AC power source and the ACS550. This
disconnect device must:
• Be sized to conform to applicable safety regulations, including, but not limited to,
both national and local electrical codes.
• Be locked in the open position during installation and maintenance work.
The disconnect device must not be used to control the motor. Instead use the control
panel, or commands to the I/O terminals for motor control.
Fuses
Branch circuit protection must be provided by the end-user, and sized per national
and local electric codes. The following tables provide fuse recommendations for
short circuit protection on the drive's input power.
Technical Data
Input Power (Mains) Connection Specifications
208/220/230/240 VAC 3-phase (or 1-phase) +10% -15% for
ACS550-x1-xxxx-2.
Voltage (U
)
1
400/415/440/460/480 VAC 3-phase +10% -15% for ACS550-x1-xxxx-4.
Maximum allowed prospective short-circuit current in the supply is 100 kA
in a second providing that the mains cable of the drive is protected with
(IEC 629)
appropriate fuses. US: 100,000 AIC.
Frequency
48...63 Hz
Imbalance
Max. ± 3% of nominal phase to phase input voltage
0.98 (at nominal load)
)
1
90 °C (194 °F) rating minimum.
Rating
ACS550 User's Manual