Level 3 - Omega Engineering CN9400 User Manual

Dual display autotune temperature controller
Table of Contents

Advertisement

LEVEL 3

OUTPUT CONFIGURATION
Note: 'Read only' after initial configuration. rSET ALL full reset to
factory settings required to change
F
unction
Options
[Factory settings] shown in brackets
[nonE]
rLY
SSd
SP1.D
Select SP1 output device
[nonE]
SSd rLY
SP2.D
Read SP2 output device
(read only)
Dual Relay and Dual SSd output options Models CN9411
and CN9422 are factory set. See page 22
Note: (when in initial configuration only)
Hold
and
or
for 10 seconds to move to or from
output devices in shaded portion.
subsequently.
SP1.D
rLY1 rLY2 SSd1
rLY2 rLY1 SSd2
Sensor burn-out/break protection
BURN
Caution: Settings affect fail safe state.
[uP.SC]
dn.SC
1u.2d
1d.2u
Select output modes: Direct/Reverse
REU.D
Caution: Settings affect fail safe state.
[1r.2d]
1d.2d
1r.2r
1d.2r
Select Reverse on SP1 for heating and Direct for
cooling applications.
SP1
SP2
Upscale
Upscale
Downscale
Downscale
Upscale
Downscale
Downscale
Upscale
SP1
SP2
Reverse
Direct
Direct
Direct
Reverse
Reverse
Direct
Reverse
19