Commissioning, inspection, maintenance
Venting the heating system
2. Activate venting program (see following steps).
Note
For function and sequence of the venting program,
see page 122.
Activating the venting function
Weather-compensated control unit
Service menu
1. Press OK and
simultaneously for approx. 4 s.
å
2. "Service functions"
3. "Venting"
Venting function is enabled.
4. Ending venting function:
Press OK or
.
ä
Filling the siphon with water
D
E
F
C
B
Fig.24
Checking all connections on the heating water side and DHW side for leaks
Checking the power supply
Designating heating circuits - only for weather-compensated control units
In the delivered condition, heating circuits are designa-
ted "Heating circuit 1", "Heating circuit 2" and "Heating
circuit 3" (if installed).
If the system user prefers, heating circuits can be re-
designated to suit the specific system.
30
(cont.)
3. Check the system pressure.
Constant temperature control unit
Service menu
1. Press OK and
2. Select "
"ON" flashes.
3. Activate the venting function with OK.
"EL on" is shown constantly.
4. Ending venting function:
Press
1. Pull off cap
2. Undo hose
3. Undo union nut
4. Fill siphon
5. Refit hose
A
6. Push on cap
To enter names for heating circuits:
simultaneously for approx. 4 s.
å
5
" with
and confirm with OK.
Ú
.
ä
downwards.
C
D
.
and pull off siphon
E
wards.
F
with water and refit.
.
D
C
from below.