Code 1

General

Accessing coding level 1
Note: Codes are displayed as plain text.
Codes that have no function due to the heating
system equipment level or the setting of other
codes are not displayed.
Heating systems with one heating circuit without
mixing valve and one or two heating circuits with
mixing valve:
The heating circuit without a mixing valve is
designated "Heating circuit 1" and the heating
circuits with mixing valve as "Heating circuit 2"
or "Heating circuit 3".
If the heating circuits were given individual designations,
the selected designation and "HC1", "HC2" or "HC3"
appear instead:
Select "General"
Coding
Coding in the factory setting
System design
00:2
System type 1:
One heating circuit
without mixing valve
A1 (heating circuit 1),
System type
Value address
00: ...
2
1
4
2
6
3, 4
8
5
10
5
42
1. Press OK and
seconds.
2. "Coding level 1"
3. Select group of required coding address:
- "General"
- "Boiler"
- "DHW"
- "Heating circuit 1/2/3"
- "All codes std device"
In this group, all coding addresses from coding level 1
(except the coding addresses from the "Solar"group)
are displayed in ascending order.
4. Select coding address.
5. Select value according to the following tables and
confirm with OK.
6. If you want to reset all codes to their factory setting:
Select "Standard setting" in "Coding level 1".
Note: This also resets codes from coding level 2.
Possible change
00:2
to
00:10
Description
One heating circuit without mixing valve A1 (heating circuit 1), (code is
adjusted automatically).
One heating circuit with mixing valve (heating circuit 2).
One heating circuit without mixing valve A1 (heating circuit 1) and one
heating circuit with mixing valve M2 (heating circuit 2), (code is adjusted
automatically).
One heating circuit with mixing valve M2 (heating circuit 2) and one

heating circuit with mixing valve M3 (heating circuit 3), (code is adjusted

automatically).
One heating circuit without mixing valve A1 (heating circuit 1), one heating
circuit with mixing valve M2 (heating circuit 2) and one heating circuit with
mixing valve M3 (heating circuit 3), (code is adjusted automatically).
Vitodens 222-F B2TB 19 and 35 Service
simultaneously for approximately 4
For system type,
see the following table:

Hide quick links: