G. Equivalent Feet of Pipe
The table below can help you calculate the equivalent feet
of pipe which is a method used to determine pellet vent size.
Figure 12.1.
3 ft.
2 ft.
Figure 12.1
H. Pipe Selection Chart
The chart will help you in determining proper venting size
according to the equivalent feet of pipe calculated previously
and the altitude above sea level of this installation.
Figure 12.2.
a. Locate the calculated equivalent feet of pipe on the vertical
left side of the chart.
b. Move to the right horizontally on the chart until you reach
your altitude above sea level.
c. If you fall below the diagonal line, 3 or 4 inch (76 to 102mm)
pipe may be used.
d. If it is anywhere above the diagonal line, a 4 inch (102mm)
diameter pipe is required.
NOTICE:
• A 90° elbow is 5 times as restrictive to the fl ow of exhaust
gases under positive pressure as 1 foot (305mm) of hori-
zontal pipe.
• A foot of horizontal pipe is twice as restrictive as a foot of
vertical pipe.
Fire Risk.
• Only LISTED venting components may be used.
• NO OTHER vent components may be used.
• Substitute or damaged vent components may impair
safe operation.
12
Example of 3 Elbow-Rear Vent Termination Calculation
2 ft.
2 ft.
WARNING
Vent surfaces get HOT, can cause burns if
touched. Non-combustible shielding or guards
may be required.
Pellet Venting
# of
Feet of
Component
Elbows
Pipe
o
90
Elbow or Tee
3
o
45
Elbow
Horizontal Pipe
Vertical Pipe
Note: This is a generic example and is not
intended to represent any specifi c fuel type.
30
Example 1
20
Equivalent Pipe
Length In Feet
Example 2
10
0
Figure 12.2
Example 1: If the equivalent length of pipe is 23 feet (7m) with
altitude of 8,000 feet (2438m) you must use 4 inch (102mm)
diameter type "L" or "PL" vent.
Example 2: If the equivalent length of pipe is 12 feet (3.7m)
with altitude of 6,000 feet (1829m) you may use 3 or 4 inch
(76 to 102mm) diameter type "L" or "PL" vent.
RISK OF INJURY OR PROPERTY DAMAGE!
Improper installation, adjustment, alteration, service or main-
tenance can cause injury or property damage.
Refer to the owner's information manual provided with this
appliance.
For assistance or additional information consult a qualifi ed
installer, service agency or your dealer.
7050-145E
WARNING
Multiplied
Equivalent
By
Feet
X
5
X
3
7
X
1
2
X
0.5
Total Equivalent Feet
4 in. (102mm) Diameter Pipe Only
3 in. or 4 in. (76mm or 102mm) Diameter Pipe
1
2
3
4
5
6
ALTITUDE IN THOUSANDS OF FEET
WARNING
Components
Equivalent Feet
15
7
1
23
7
8
9
10
August 3, 2015

Advertisement

Table of Contents
loading

Table of Contents