Supplementary Explanation
1.1.7
Field Setting
(Example of setting operation)
Centralized control
1. Press
group No. setting
2. Set mode No. to "00" using
(mode No.: 00)
3. Set centralized control group No. using
4. Enter displayed group No. by pressing
5. Press
Centralized control
For group control, the following step must be performed.
group No. setting
(*) Set unit No. using
(mode No.: 30)
Procedure for
entering individual
settings (mode No.:
44)
< Example >
This setting method can be used when a group control system is connected with units having a different
airflow capacity from other units in the system.
1. Press
2. Set mode No. to "44" using
3. Set unit No. using
4. Set airflow volume (ventilation mode) using
5. Set airflow direction (ventilation volume) using
6. Enter settings by pressing
62
for more than 4 seconds.
to return to normal operation mode.
.
The setting is generally the same for all units in the same group control system. However, the setting of
selected units can be fixed by the following method.
Ventilation volume
at High
for more than 4 seconds.
.
Unit No.
Airflow volume
Airflow direction
(air conditioner)
(air conditioner)
or
.
[
] or
.
Unit No.
Airflow volume
(air conditioner)
High
High
Ventilation volume fixed at Low
or
.
[
].
[
.
Mode No.
Ventilation volume
(heat recovery ventilation unit)
[
].
(HL053)
Mode No.
Low
(HL054)
].
Ventilation mode
(heat recovery ventilation unit)
(HL055)
Supplementary Explanation
SiE71-202