32
EN EN
* Within the appliance enclosure a 3" (152mm)
clearance between the top of the vent pipe
and combustible materials is required. All other
clearances within the enclosure, including
where the vent pipe exits the enclosure are
subject to 2" (51mm) to the sides and bottom
and 3" (76mm) to the top for horizontal and 1"
(25mm) for vertical.
** See "VENTING" section.
W415-1539 / A / 04.19.16
TOP OF ENCLOSURE
(COMBUSTIBLE)
STEEL STUD
FRAME
63 1/2"
1613mm
26 9/16"
MINIMUM
675mm
ENCLOSURE
MINIMUM
HEIGHT
TOP OF
APPLIANCE
25 5/8"
OPENING
651mm
MINIMUM
COMBUSTIBLE
3"
152mm *
HEAT
SHIELD
51mm
STEEL STUD
MINIMUM
FRAME
ENCLOSURE
HEIGHT
MINIMUM
HEIGHT
OF
NON-COMBUSTIBLE
MATERIAL
NON-COMBUSTIBLE
3"
0" IF NON-COMBUSTIBLE
76mm
FINISHING IS USED SUCH
AS BRICK AND STONE.
2"
51mm
57"
1448mm
MINIMUM
PLUS RISE**
2"
TOP OF ENCLOSURE
(COMBUSTIBLE)
HEAT SHIELD
NON-COMBUSTIBLE
MATERIAL