Introduction; Features Of The Option 11C Power Supply; Dimensions And Weight; Ac/Dc Power Supply Features - Meridian Nortel 1 Option 11C Technical Reference Manual

Nortel networks network system technical reference guide
Hide thumbs Also See for Nortel Meridian 1 Option 11C:
Table of Contents

Advertisement

Page 198 of 544

Introduction

Features of the Option 11C power supply

Dimensions and weight

AC/DC power supply features

553-3011-100
Standard 14.00
Power supplies
AC power supply features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
Voltage . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
Over-voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
Under-voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
This chapter describes the Option 11C AC/DC power supplies (NTAK04,
NTAK05, NTDK72, and NTDK78) reserve power requirements, and the
operation of the Power Fail Transfer Unit (PFTU). The NTDK15 power
supply for the Option 11C Mini is described on page 204.
The AC/DC and DC power supplies measure approximately 12.5 inches
(305 mm) high, 5 inches (127 mm) wide and 10 inches (245 mm) deep.
It weighs approximately 12 lb (5.5 kg), while the DC power supply weighs
approximately 8 lb (3.5 kg).
The NTAK04 and NTDK78 AC/DC power supply has the following features:
A current limiting circuit which limits the surge of current on the input
line when the system is first switched on.
Accommodates a reserve power system. The system continues to operate
on DC reserve power in case of AC power failure.
Note: The NTAK04 or NTDK78 AC/DC power supply cannot power up
on battery alone. If the NTAK04 or NTDK78 is powered down while
operating on DC reserve power, then AC power is required to power up
the system.
Battery charging for the reserve power system. Charging current in a
worst-case scenario (when Meridian Mail is installed) is 1.0 amp.
Power (± 15V) for one attendant console.
Generation of a system line transfer signal and power (-52V) for the
Power Fail Transfer Unit (250 MA maximum).