4. R.V. coil control
Heating · · · · · ON
Cooling · · · · · OFF
Dry · · · · · · · · OFF
NOTE : The 4-way valve reverses for 5 seconds right before start-up of the compressor.
Operation time chart
Compressor
R.V. coil
Outdoor fan
8-2. COOL (
) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button. OPERATION INDICATOR
lamp of the indoor unit turns on with a beep tone.
(2) Select COOL mode with the OPERATION SELECT button.
(3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button)
to select the desired temperature.
The setting range is 16 ~ 31°C.
1. Indoor fan speed control
Indoor fan speed control is as same as COOL mode of "I FEEL CON-
TROL".(Refer to 8-1-1. COOL mode of I FEEL CONTROL"- 1.)
2. Coil frost prevention
Coil frost prevention is as same as COOL mode of "I FEEL CON-
TROL".(Refer to 8-1-1. COOL mode of I FEEL CONTROL"- 2.)
8-3. DRY (
) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a
beep tone.
(2) Select DRY mode with the OPERATION SELECT button.
(3) The microprocessor reads the room temperature and determines the
set temperature. Set temperature is as shown on the right chart.
(4)DRY operation will not function when the room temperature is 13°C or below.
1. Indoor fan speed control
Indoor fan speed control is as same as DRY mode of "I FEEL CONTROL".(Refer to 8-1-2. DRY mode of I FEEL
CONTROL"- 1.)
2. The operation of the compressor and indoor / outdoor fan
The operation of the compressor and indoor / outdoor fan is as same as DRY mode of "I FEEL CONTROL".(Refer to 8-1-2.
DRY mode of I FEEL CONTROL"- 2.)
3. Coil frost prevention
Coil frost prevention is as same as DRY mode of "I FEEL CONTROL".(Refer to 8-1-2. DRY mode of I FEEL CONTROL"- 3.)
8-4. HEAT (
) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select HEAT mode with the OPERATION SELECT button.
(3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature.
The setting range is 16 ~ 31°C.
1. Indoor fan speed control
Indoor fan speed control is as same as HEAT mode of "I FEEL CONTROL".(Refer to 8-1-3. HEAT mode of I FEEL
CONTROL"- 1.)
2. High pressure protection
High pressure protection is as same as HEAT mode of "I FEEL CONTROL".(Refer to 8-1-3. HEAT mode of I FEEL
CONTROL"- 2.)
3. Defrosting
Defrosting is as same as HEAT mode of "I FEEL CONTROL".(Refer to 8-1-3. HEAT mode of I FEEL CONTROL"- 3.)
4. R.V. coil control
R.V.coil control is as same as HEAT mode of "I FEEL CONTROL".(Refer to 8-1-3. HEAT mode of I FEEL
CONTROL"- 4.)
(COOL / DRY)
5 sec.
ON
OFF
ON
OFF
ON
OFF
34
(HEAT)
5 sec.
ON
OFF
ON
OFF
ON
OFF
Set temperature and
:
initial room temperature in dry mode
35
30
25
20
15
10
10
15
20
Initial room temperature
25
30
35
: