NOTES:
Connect other devices that require 12 Vdc to VX1
(TB4-1,2 or VX2 (TB5-1,2) for power and connect
the ISP COM TxRx- (TB4-3) and TxRx+ (TB4-3)
to CU COM 1 or 2, but not both.
The RS485 COM Port connector (J1) is only
intended for use by field personnel for a tempo-
rary CC2 plug-in. Note that power is derived from
VX1 and the COM is the same COM used for the
ISP. (This connection is not usually used since
learning can be done using PRO9000.) The fol-
lowing restrictions apply:
RETAINING CLIP
1041-004
TRACK
ENCLOSURE
SIDE
SIDE
4 MOUNTING HOLES
FOR NO. 8 ROUND
PAN HEAD SCREWS
POWER SUPPLY ASSEMBLY
GROUND
LUG
1
INSTALL AND SECURELY MOUNT RRI COMMUNICATION INTERFACE MODULES USING THE PLASTIC TRACK (INCLUDED) AS SHOWN. TWO TRACKS MAY BE
SUSPENDED FROM THE TOP EDGE OF THE INTELLIGUARD ENCLOSURE OR ONE TRACK MAY BE INSTALLED ON THE RIGHT SIDE NEXT TO THE BATTERY.
RS-232 to RS-485 Interface (RRI) 8003-321
The RS-232 to RS-485 Interface (RRI) 8003-321 is used to
extend the I9000 (COM 3) to the EBI communication link for
distances in excess of 50 feet. This distance can be extended
to 3277 feet (999M) using the RS-485 with the RRI.
1/2 IN. (13 MM) KNOCKOUT (4 PLACES)
PLASTIC TRACK
7/8 IN. (22 MM), DIAMETER
7003-217
1
BATTERY 12V, 7.0 Ah
YUASA NO. NP7-12
HPS NO. 4002-037
OR EQUIVALENT
Fig. 19. RRI mounting locations.
1. Maximum number of devices is 31 for either COM 1 or
COM 2.
2. Maximum number of CC2s on the system must not
exceed four.
3. A free CC2 address is required to prevent conflicts with
other CC2s (disconnect another CC2 temporarily, if nec-
essary).
See Fig.19 to install the RRI Communication Interface
Modules.
INTELLIGENT COMMUNICATIONS
PROCESSOR (ICP)
BATTERY 12V, 7.0 Ah
YUASA NO. NP7-12
HPS NO. 4002-037
OR EQUIVALENT
The 8003-321 Assembly is required for the Pseudo RS-232 to
RS-485 Interface installation. The Assembly includes the
following parts: Plastic Track, Part no. 7003-217, Retaining
Clip, Part No. 1041-004 and Pseudo RS-232 to RS-485
Interface (RRI), Part No. 8003-322.
19
INTELLIGUARD 9000™
INTELLIGUARD ENCLOSURE
TAMPER SWITCH
5115-094
TB1
TB2
M14497A
74-3047—1
1