INTELLIGUARD 9000™
MOUNT THE HEDS IV
See Fig. 7 for a typical door-mounted HEDS IV.
1. Remove the HEDS IV magnet assembly cover and the
two magnets by loosening the two set screws (requires
hex allen key). This allows access to the mounting holes
located under the magnets.
2. Mount the magnet assembly on the door at the selected
mounting location (as far away from the hinge side as
possible) using two No. 6 round or pan head screws.
3. Reinstall the two magnets (red markings on magnets
must be facing toward the support closest to the edge of
the plastic base and flush with the support) and tighten
the two set screws.
HEDS IV COMPLETE
ASSEMBLY 8003-283
(INCLUDES SENSOR
AND MAGNET ASSEMBLY)
SENSOR 8003-280
MAGNET ASSEMBLY
8003-282
HEDS IV
BOTTOM
(CONTAINS
MAGNET)
Fig. 7. HEDS IV typical door mount position.
4. Reinstall the cover.
5. Remove the L shaped cover of the HEDS IV unit
assembly. See Fig. 8.
6. Select one of the cable entry options shown in Fig. 8
and drill or bend the cable entries.
7. Align the HEDS IV unit assembly with the HEDS IV
magnet assembly and mount using two flat head
screws. The spacing between both units must not
exceed 3/16 in. (4.76 mm). Do not allow the two parts to
touch when the door is closed.
8. Feed the cable(s) into the unit.
9. Connect the wires to the terminals as indicated in Fig. 6.
10. Do not install the L shaped cover until the device is cali-
brated and learned.
74-3047—1
KNOCKOUT
DOOR
HEDS IV
TOP
11. Learn the HEDS IV using step 11a. or 11b.
a. With the protected door open, start the LEARNING
Mode (DEVICES WITH SERIAL #) at a CC2. Press
and hold the HEDS IV learn push button S1 for one
second. This also starts the calibration process. At
the CC2, end the learning procedure and proceed to
step 12b.
b. Take note of the HEDS IV serial number, enter it
(gathered information from all devices, enter and
download once to save time) into PRO 9000 and
download it into the I9000.
12. Calibrate the HEDS IV.
a. With the protected door open, press and hold S1 for
one second.
b. Replace the HEDS IV cover.
c. Close the door.
d. Send the Reset Detector command from the CC2.
13. Repeat steps 1 through 12 for each HEDS IV.
14. From the CC2, exit the CONFIGURATION Menu for
changes to become effective.
ONE CORNER OF THE PLASTIC KNOCKOUT IS LIFTED AND BENT
OVER. CHOOSE THE CORNER WHICH IS MOST CONVENIENT.
DRILL ONE OR TWO HOLES AS
REQUIRED ANYWHERE ON THIS
SURFACE. VERIFY FOR OBSTACLES
ON OPPOSITE SIDE FIRST.
M16108
DRILL ONE OR TWO HOLES AS
REQUIRED — HERE OR ON OPPOSITE END.
Fig. 8. Cable entry options.
6-Input/Output Concentrators (BIC-6)
Most detection devices connect to a 6-Input Concentrator
(BIC-6). Each BIC-6 accepts a maximum of six inputs and
relays the signal to the CU as a single output to reduce the
amount of direct wiring to the CU. Each CU supports a
maximum of 31 BIC-6s on each COM, for a total of 62. These
totals include all device types shown in Fig. 2. Fig. 9 shows
wiring terminals and programming buttons on a BIC-6.
.To install the BIC-6:
1. Remove the BIC-6 cover at the selected mounting loca-
tion.
2. Use a no. 1 Robertson (square drive) screwdriver to
remove the screws securing the circuit board to the
back casing.
IMPORTANT
Touch a grounded object to ensure you are not elec-
trostatically charged before handling the circuit
board.
8
8003-280 UNIT ASSEMBLY
(ENCLOSURE ONLY)
COVER
(NON-REMOVABLE)
M14547