Mitsubishi Electric F700 Instruction Manual page 76

Hide thumbs Also See for F700:
Table of Contents

Advertisement

Parameter
Name
Analog input
73
selection
Terminal 1 added
compensation
242
amount (terminal 2)
Terminal 1 added
compensation
243
amount (terminal 4)
Override bias
252
Override gain
253
Terminal 4 input
267
selection
4mA input check
573
selection
Input filter time
74
constant
Reset selection/
disconnected PU
75
detection/PU stop
selection
Alarm code output
76
selection
Incre
Initial
Range
ments
Value
You can select the input specifications of
terminal 2 (0 to 5V, 0 to 10V, 0 to 20mA)
and input specifications of terminal 1 (0 to
±5V, 0 to ±10V).
To change the terminal 2 to the voltage
0 to 7,
1
1
input specification (0 to 5V/ 0 to 10V), turn
10 to 17
OFF(initial status) the voltage/current
input switch 2. To change it to the current
input(0 to 20mA), turn ON the voltage/
current input switch 2. Override and
reversible operation can be selected.
Set the ratio of added compensation
0.1%
100%
0 to 100%
amount when terminal 2 is the main
speed.
Set the ratio of added compensation
0.1%
75%
0 to 100%
amount when terminal 4 is the main
speed.
Set the bias side compensation value of
0.1%
50%
0 to 200%
override function.
Set the gain side compensation value of
0.1%
150%
0 to 200%
override function.
Terminal 4 input 4 to
0
20mA
1
0
Terminal 4 input 0 to
1
5V
Terminal 4 input 0 to
2
10V
When the current input drops to or below
2mA, the LF signal is output and inverter
1
continues operation at the frequency just
1
9999
before current reaches 2mA.
9999
4mA input is not checked.
The primary delay filter time constant for
1
1
0 to 8
the analog input can be set.
A larger setting results in a larger filter.
You can select the reset input
acceptance, disconnected PU (FR-
DU07/FR-PU04/FR-PU07) connector
detection function and PU stop
function, and reset restriction (01800 or
0 to 3,
more).
14 to 17
1
14
For the initial value, reset always
100 to 103,
enabled, without disconnected PU
114 to 117*
detection, with PU stop function, and
without reset restriction (01800 or
more) are set.
* 100 to 103 and 114 to 117 can be set only
0
Without alarm code output
1
With alarm code output
1
0
Alarm code output at alarm occurrence
2
only
Description
Turn ON the
voltage/current
input switch 1
(initial status).
Turn OFF the
voltage/current
input switch 1.
01800 or more
for
.
Parameter list
All
Param
Param
param
eter
eter
eter
copy
clear
clear
: enabled
× : disabled
×
×
4
×
×
71