3
Capacity tables
RKS+FLKS50B
Cooling capacity
Indoor
EWB
EDB
20
(°C)
(°C)
TC
SHC
14.0
20
4.96
3.26
1.37
16.0
22
5.12
3.30
1.40
18.0
25
5.27
3.33
1.42
19.0
27
5.35
3.35
1.44
22.0
30
5.58
3.40
1.47
24.0
32
5.74
3.43
1.50
RKS+FFQ50B
Cooling capacity
Indoor
EWB
EDB
20
(°C)
(°C)
TC
SHC
14.0
20
4.76
3.51
1.45
16.0
22
4.92
3.54
1.48
18.0
25
5.07
3.58
1.50
19.0
27
5.15
3.59
1.52
22.0
30
5.38
3.65
1.55
24.0
32
5.54
3.68
1.58
RKS+FFQ60B
Cooling capacity
Indoor
EWB
EDB
20
(°C)
(°C)
TC
SHC
14.0
20
5.86
4.30
1.72
16.0
22
6.02
4.34
1.75
18.0
25
6.17
4.37
1.77
19.0
27
6.25
4.39
1.79
22.0
30
6.48
4.44
1.82
24.0
32
6.64
4.47
1.85
SYMBOLS
AFR:
Air flow rate
BF:
Bypass factor
EWB:
Entering wet bulb temp.
EDB:
Entering dry bulb temp.
TC:
Total capacity
SHC:
Sensible heating capacity
PI:
Power input
• Pair Application, Inverter Controlled Unit • R-410A • RKS50-60-71BVMB9
25
PI
TC
SHC
PI
TC
4.81
3.19
1.47
4.66
4.97
3.23
1.49
4.82
5.12
3.26
1.52
4.97
5.20
3.28
1.53
5.05
5.43
3.33
1.57
5.28
5.59
3.36
1.60
5.44
25
PI
TC
SHC
PI
TC
4.61
3.44
1.55
4.46
4.77
3.47
1.57
4.62
4.92
3.51
1.60
4.77
5.00
3.52
1.61
4.85
5.23
3.58
1.65
5.08
5.39
3.61
1.68
5.24
25
PI
TC
SHC
PI
TC
5.71
4.23
1.82
5.56
5.87
4.27
1.84
5.72
6.02
4.30
1.87
5.87
6.10
4.32
1.88
5.95
6.33
4.37
1.92
6.18
6.49
4.40
1.95
6.34
3
(m
/min)
(°CWB)
(°CDB)
(kW)
(kW)
(kW)
• Split - Sky Air • Outdoor Units
230V [50Hz]
Outdoor temperature (°C)
30
32
SHC
PI
TC
SHC
PI
3.12
1.56
4.60
3.09
1.60
3.16
1.59
4.76
3.13
1.62
3.19
1.61
4.91
3.16
1.65
3.21
1.63
4.99
3.18
1.66
3.26
1.66
5.22
3.23
1.70
3.29
1.69
5.38
3.26
1.73
230V [50Hz]
Outdoor temperature (°C)
30
32
SHC
PI
TC
SHC
PI
3.37
1.64
4.40
3.34
1.68
3.40
1.67
4.56
3.38
1.70
3.44
1.69
4.71
3.41
1.73
3.45
1.71
4.79
3.43
1.74
3.51
1.74
5.02
3.48
1.78
3.54
1.77
5.18
3.51
1.81
230V [50Hz]
Outdoor temperature (°C)
30
32
SHC
PI
TC
SHC
PI
4.16
1.91
5.50
4.13
1.95
4.20
1.94
5.66
4.17
1.97
4.23
1.96
5.81
4.20
2.00
4.25
1.98
5.89
4.22
2.01
4.30
2.01
6.12
4.27
2.05
4.33
2.04
6.28
4.30
2.08
NOTES
1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat
2.
Shows nominal cooling capacities and power input
3. TC, PI and SHC must be calculated by interpolation using the figures in the
above tables. (Figures out of the tables should not be used for calculation.)
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
3
SHC* = 0.02 x AFR (m
/min) x (1-BF) x (DB-EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Corresponding refrigerant piping length:
Level difference:
6. Air flow rate (AFR) and Bypass factor (BF) are taburated above.
AFR
BF
35
40
TC
SHC
PI
TC
SHC
4.51
3.05
1.66
4.36
2.98
4.67
3.09
1.68
4.52
3.02
4.82
3.12
1.71
4.67
3.05
4.90
3.14
1.72
4.75
3.07
5.13
3.19
1.76
4.98
3.12
5.29
3.22
1.79
5.14
3.15
AFR
BF
35
40
TC
SHC
PI
TC
SHC
4.31
3.30
1.74
4.16
3.23
4.47
3.33
1.76
4.32
3.26
4.62
3.37
1.79
4.47
3.30
4.70
3.38
1.80
4.55
3.31
4.93
3.44
1.84
4.78
3.37
5.09
3.47
1.87
4.94
3.40
AFR
BF
35
40
TC
SHC
PI
TC
SHC
5.41
4.09
2.01
5.26
4.02
5.57
4.13
2.03
5.42
4.06
5.72
4.16
2.06
5.57
4.09
5.80
4.18
2.07
5.65
4.11
6.03
4.23
2.11
5.88
4.16
6.19
4.26
2.14
6.04
4.19
7.5 m
0 m
1
11.4
3
0.18
PI
1.75
1.78
1.80
1.82
1.85
1.88
3D040893
12.0
0.16
PI
1.83
1.86
1.88
1.90
1.93
1.96
3D041022
15.0
0.11
PI
2.10
2.13
2.15
2.17
2.20
2.23
3D041027
7