Daikin RKS50BVMB9 Technical Data Manual page 6

Hide thumbs Also See for RKS50BVMB9:
Table of Contents

Advertisement

2
Specifications
1
2
ELECTRICAL DATA
RKS+FTKS50B
Indoor unit
FTKS50BVMB
RKS+FTKS60B
RKS+FTKS71B
Indoor unit
FTKS60BVMB
FTKS71BVMB
RKS+FVKS50B
Indoor unit
FVKS50BVMB
RKS+FLKS50B
Indoor unit
FLKS50BVMB
RKS+FFQ50B
RKS+FFQ60B
Indoor unit
FFQ50BV1B
FFQ60BV1B
SYMBOLS
MCA
: Min. Circuit Amps (A)
MFA
: Max. Fuse Amps (A)
RHz
: Rated operating frequency(Hz)
RLA
: Rated Load Amps (A)
OFM
: Outdoor Fan Motor
IFM
: Indoor Fan Motor
FLA
: Full Load Amps
W
: Rated motor output (W)
4
• Pair Application, Inverter Controlled Unit • R-410A • RKS50-60-71BVMB9
Outdoor unit
Hz-Volts
RKS50BVMB9
50-230
Outdoor unit
Hz-Volts
RKS60BVMB9
50-230
RKS71BVMB9
50-230
Outdoor unit
Hz-Volts
RKS50BVMB9
50-230
Outdoor unit
Hz-Volts
RKS50BVMB9
50-230
Outdoor unit
Hz-Volts
RKS50BVMB9
50-230
RKS60BVMB9
50-230
• Split - Sky Air • Outdoor Units
Power supply
Voltage range
MCA
MFA
MAX. 50Hz 253V
18
20
MIN. 50Hz 207V
Power supply
Voltage range
MCA
MFA
MAX. 50Hz 253V
18
20
MIN. 50Hz 207V
MAX. 50Hz 253V
16.8
20
MIN. 50Hz 207V
Power supply
Voltage range
MCA
MFA
MAX. 50Hz 253V
18
20
MIN. 50Hz 207V
Power supply
Voltage range
MCA
MFA
MAX. 50Hz 253V
18
20
MIN. 50Hz 207V
Power supply
Voltage range
MCA
MFA
MAX. 50Hz 253V
18
20
MIN. 50Hz 207V
MAX. 50Hz 253V
18
20
MIN. 50Hz 207V
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
5. For more details concerning conditional connections, see
http://www.daikineurope.com/extranet, select ''Daikin
Documentation'' and select ''conditional connection'', ''the requested
product type'' and ''English'' from the drop down lists, click the search
button.
Finally, click on the document title of your choice.
Compressor
OFM
RHz
RLA
W
FLA
72
6.92
53
0.18
Compressor
OFM
RHz
RLA
W
FLA
72
8.86
53
0.24
80
10.58
53
0.26
Compressor
OFM
RHz
RLA
W
FLA
76
7.04
53
0.18
Compressor
OFM
RHz
RLA
W
FLA
75
7.00
53
0.18
Compressor
OFM
RHz
RLA
W
FLA
72
7.43
53
0.18
85
8.45
53
0.24
IFM
W
FLA
40
0.16
3D040876
IFM
W
FLA
43
0.16
43
0.18
3D040877
IFM
W
FLA
14+14
0.31
3D040876
IFM
W
FLA
34
0.54
3D040876
IFM
W
FLA
55
0.7
55
0.7
3D041020