11

Installation

RKS50,60,71B
Model
Max. allowable length
Max. allowable height
Additional refrigerant required
for refrigerant pipe exceeding
10 m in length.
Gas pipe
Liquid pipe
* Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced performance.
In sites with poor drainage, use block
bases for outdoor unit. Adjust foot
height until the unit is leveled. Otherwise,
water leakage or pooling of water may
occur.
• Pair Application, Inverter Controlled Unit • R-410A • RKS50-60-71BVMB9
Outdoor unit installation drawings
50 class
60 class
71 class
30m
20m
20 g/m
O.D. 12.7 mm
O.D. 9.5 mm
O.D. 6.4 mm
Foot bolt-hole centres
From unit's side
• Split - Sky Air • Outdoor Units
Service lid
250 mm from wall
Foot bolt-hole
Allow space for piping and electrical
centres
servicing.
Where there is a danger of the unit falling, use foot
bolts, or wires.
1
11
Wrap the installation pipe with the
finishing tape from bottom to top
19