Floor Protection; Tools For Installation - New Buck Corporation Heater Model 80 Installation And Operation Manual

Buck stove heater model 80 operation manual
Table of Contents

Advertisement

MODEL 80
Minimum Clearances
The New Buck Corporation Model 80 must be installed in compliance with the instructions contained in this
manual.
Clearance from combustible walls and ceilings. (Using single wall chimney connector)
The minimum lateral distance between any part of the room heater and combustible wall is shown in Figures 6 and
7.
FIGURE 6
FIGURE 7

FLOOR PROTECTION

If a freestanding model is to be installed on a combustible floor, a non-combustible pad must be placed below it to
protect the floor from burning material from the stove. The pad must be 37" wide by 37 1/2" deep. Floor protector
must be 3/8" in minimum thickness, non-combustible material or equivalent.
The unit must be positioned on the pad so that there is a minimum of 16" from the front of the door opening to the
front of the pad, and a minimum of 8" measured horizontally from the sides of the fuel loading and ash removal
openings to the sides of the pad.
NOTE: For clearance reductions using wall protectors, refer to the NFPA-211 Code.

TOOLS FOR INSTALLATION

Drop Cloth
Electric Drill with 7/32" drill bit
1/2" - 9/16" combination wrench
3/8" magnetic socket chuck adapter, 3/8" wrench (box or socket) or adjustable wrench
Socket Set
Tape Measure
Pencil
Level
Screw Driver