Discharge Pipe Temperature Control - Daikin FTXS60GV1B Service Manual

Inverter pair wall mounted type g-series
Hide thumbs Also See for FTXS60GV1B:
Table of Contents

Advertisement

Troubleshooting

4.17 Discharge Pipe Temperature Control

F3
Error Code
Method of Error
An error is determined with the temperature detected by the discharge pipe thermistor.
Detection
Error Decision
Conditions
60 class
71 class
Supposed
Causes
Troubleshooting
Check No.01
Refer to P.102
Check No.12
Refer to P.104
Check No.14
Refer to P.105
86
If the temperature detected by the discharge pipe thermistor rises above A°C, the
compressor stops.
The error is cleared when the discharge pipe temperature has dropped below B°C.
A (°C)
110
120
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Defective discharge pipe thermistor
(Defective outdoor heat exchanger thermistor or outdoor temperature thermistor)
Defective electronic expansion valve or coil
Refrigerant shortage
Defective four way valve
Water mixed in refrigerant
Defective stop valve
Defective outdoor unit PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check No. 01
Check the thermistors.
OK
Check No. 12
Check the electronic
expansion valve.
OK
Check No. 14
Check the refrigerant
line.
OK
B (°C)
95
107
NG
Discharge pipe thermistor
Outdoor heat exchanger thermistor
Outdoor temperature thermistor
NG
NG
Refrigerant shortage
Four way valve
Water mixed
Stop valve
SiBE041011_A
Replace the
defective
thermistor(s).
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB.
(R15825)
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents