Home Layout - York GY9S Installation Manual

High efficiency tubular heat exchanger series
Table of Contents

Advertisement

VENT CLEARANCES
D
E
B
L
FIGURE 12: Home Layout
A. Clearance above grade, veranda, porch, deck, or
balcony
B. Clearance to window or door that may be opened
C. Clearance to permanently closed window
D. Vertical clearance to ventilated soffit located
above the terminal within a horizontal distance
of 2 feet (61 cm) from the center line of the terminal
E. Clearance to unventilated soffit
F. Clearance to outside corner
G. Clearance to inside corner
H. Clearance to each side of center line
extended above meter/regulator assembly
I. Clearance to service regulator vent outlet
J. Clearance to nonmechanical air supply
inlet to building or the combustion
air inlet to any other appliance
K. Clearance to a mechanical supply inlet
L. Clearance above paved sidewalk or paved
driveway located on public property
M. Clearance under veranda, porch, deck, or balcony
Dryer Vent **
Plumbing Vent Stack **
Gas Appliance Vent Terminal **
Vent Termination from any Building Surface
Above anticipated snow depth
A. Clearance above grade, veranda, porch, deck, or
balcony
B. Clearance to window or door that may be opened
C. Clearance to permanently closed window
D. Vertical clearance to ventilated soffit located
above the terminal within a horizontal distance
of 2 feet (61 cm) from the center line of the terminal
1.
In accordance with the current CSA B149.1-00, Natural Gas and Propane Installation Code.
2.
In accordance with the current ANSI Z223.1 / NFPA 54, National Gas Code.
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor. For clearance not specified in ANSI Z223.1 / NFPA
54 or CSA B149.1-00.
Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation Manual.
Any fresh air or make up inlet for dryer or furnace area is considered to be forced air inlet.
Avoid areas where condensate drippage may cause problems such as above planters, patios, or adjacent to windows where steam may cause fogging.
A terminus of a vent shall be either:
Fitted with a cap in accordance with the vent manufacturer's installation instructions, or In accordance with the installation instructions for a special venting system.
* Does not apply to multiple installations of this furnace model. Refer to "VENTING MULTIPLE UNITS" in this section of these instructions.
IMPORTANT: Consideration must be given for degradation of building materials by flue gases. Sidewall termination may require sealing or shielding of building surfaces
with a corrosion resistant material to protect against combustion product corrosion. Consideration must be given to wind direction in order to prevent flue products and/or
condensate from being blown against the building surfaces. If a metal shield is used it must be a stainless steel material at a minimum dimension of 20 inches. It is rec-
ommended that a retaining type collar be used that is attached to the building surface to prevent movement of the vent pipe.
Responsibility for the provision of proper adequate venting and air supply for application shall rest with the installer.
Vent shall extend high enough above building, or a neighboring obstruction, so that wind from any direction will not create a positive pressure in the vicinity of the vent.
Unitary Products Group
G
V
A
H
FIXED
CLOSED
B
B
B
I
M
V
C
V
X
V
V
J
V
B
F
B
OPERABLE
Canadian Installations
12 inches (30 cm)
12 inches (30 cm) for models <100,000
BTUH (30 kW), 36 inches (91 cm) for
models >100,000 BTUH (30 kW)
4 Feet
4 Feet
12 Inches
12 Inches
12 Inches (two-pipe), 6 Feet (one-pipe)
3 feet (91 cm) within a height 15 feet
(4.5 m) above the meter/regulator assembly
3 feet (91 cm)
12 inches (30 cm) for models <100,000
BTUH (30 kW), 36 inches (91 cm) for
models >100,000 BTUH (30 kW)
6 feet (1.83 m)
7 feet (2.13 m)
12 inches (30 cm)
3 ft (91.44 cm)
3 ft (91.44 cm)
3 ft (91.44 cm) *
12" (30.4 cm)
12" (30.4 cm)
12 inches (30 cm)
12 inches (30 cm) for models <100,000
BTUH (30 kW), 36 inches (91 cm) for
models >100,000 BTUH (30 kW)
4 Feet
4 Feet
V
VENT TERMINAL
X
AIR SUPPLY
AREA WHERE TERMINAL IS NOT PERMITTED
X
V
K
FIXED
CLOSED
1
105561-UIM-B-0605
2
US Installation
12 inches (30 cm)
Two-pipe (direct vent) applications: 9 inches
(23 cm) for models <50,000 BTUH (15 kW),
12 inches (30 cm) for models >50,000 BTUH
(15 kW). Single-pipe applications: 4 feet.
4 Feet
4 Feet
12 Inches
12 Inches
12 Inches (two-pipe), 6 Feet (one-pipe)
3 feet (91 cm) within a height 15 feet
(4.5 m) above the meter/regulator assembly
3 feet (91 cm)
Two-pipe (direct vent) applications: 9 inches
(23 cm) for models <50,000 BTUH (15 kW),
12 inches (30 cm) for models >50,000 BTUH
(15 kW). Single-pipe applications: 4 feet.
3 feet (91 cm) above if within 10 feet (3 cm)
horizontally
7 feet (2.13 m)
12 inches (30 cm)
3 ft (91.44 cm)
3 ft (91.44 cm)
3 ft (91.44 cm) *
12" (30.4 cm)
12" (30.4 cm)
12 inches (30 cm)
Two-pipe (direct vent) applications: 9 inches
(23 cm) for models <50,000 BTUH (15 kW),
12 inches (30 cm) for models >50,000 BTUH
(15 kW). Single-pipe applications: 4 feet.
4 Feet
4 Feet