Section 24. Accessories; Section 25. Other Information And Publications - Thermo Pride Thermo Pace Downflow/Horizontal Furnace Installer's Information Manual

Table of Contents

Advertisement

5.
Locate five blower motor wires that feed through casing
hem.
6.
Label blower motor wires for proper replacement.
7.
Disconnect blower motor wires from Fan Timer. See
Figure 32.
8.
Remove 2 screws holding blower door in place.
Remove blower door.
9.
Pull blower motor wires through casing hem.
10. Remove power-disconnect assembly located in the
middle of blower deck.
11. Remove 2 screws holding blower assembly to blower
deck.
12. Slide blower assembly out.
13. After cleaning blower assembly, re-assemble in
reverse order making sure speed selections are in
original positions.
14. Install the vent assembly into the inducer rubber
coupling and tighten the hose clamps. The cut vent
pipes must be joined using a PVC coupling or rubber
coupling available from manufacturer.

SECTION 24. ACCESSORIES

THERMOSTATS: Quality thermostats are available from
the furnace manufacturer. Choose from the T87 (round
w/subbase), T834 (heating and cooling) or the T8699
(Chronotherm III)--available in white only.
PROPANE CONVERSION KIT (BELOW 6,000 ft): Includes
propane regulator-spring kit, propane pilot orifice and main
burner orifices.
HIGH-ALTITUDE PROPANE CONVERSION KIT (ABOVE
6000 FEET): Includes propane regulator-spring kit, propane
pilot orifice, main burner orifices, and high-altitude pressure
switch.
NATURAL GAS CONVERSION KIT (BELOW 6,000 ft):
Includes natural gas regulator-spring kit, natural gas pilot
orifice and main burner orifices.
HIGH-ALTITUDE NATURAL GAS CONVERSION KIT
(ABOVE 6000 FEET): Includes natural gas regulator-spring
kit, natural gas pilot orifice, main burner orifices and high-
altitude pressure switch.
COMBUSTIBLE FLOOR BASE:
installation on wooden flooring. (Not required for horizontal
installations).
DOWNFLOW FILTER KIT: Filter support mounts between
furnace and downflow return plenum. Requires an access
Page 32
Required for downflow
panel in plenum. Includes two 16" x 20" x 1" high-velocity,
washable filters.
FILTERS: High-velocity washable filters, available in
cartons of 10.
RUBBER COUPLINGS AND CLAMPS: May be installed in
vent system to provide easier blower access. Each kit
contains five sets of 2 couplings and 4 hose clamps.
SECTION 25. OTHER
INFORMATION AND
PUBLICATIONS
These publications can help you install the fu rnace. You
can usually find these at your local library or buy them
directly from the publisher. Be sure to consult current
edition of each standard.
National Fuel Gas Code
Canadian Installation Codes
National Electrical Code
Canadian Electrical Code
Standard For The Installation
Of Warm Air Heating And Air
Conditioning Systems.
For more information, contact these publishers:
American National Standards Institute Inc.
ANSI:
1430 Broadway
New York, New York 10018
(212) 642-4900
Canadian Standards Association
CSA:
178 Rexdale Boulevard
Rexdale, Ontario, Canada M9W 1R3
(416) 447-4044
American Society Of Heating Refrigeration And
ASHRAE:
Air-Conditioning Engineers, Inc.
1791 Tullie Circle N.E.
Atlanta, GA 30329
(404) 636-8400
NFPA:
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02269
(617) 770-3000
ANSI Z223.1/NFPA 54
CAN/CGA B149
ANSI/NFPA Code 70
CSA C22.1
ASHRAE/NFPA 90
Installer's Information Manual