5
Outdoor unit

5-10. PMV Kit

PMV-Kit (RBM-PMV0362E/RBM-PMV0902E) shall be required for quieter place application as an optional to reduce
refrigerant sound especially in oil retrieval control or in transient operation as start up.
5-10-1. Selection
Model name
Indoor unit capacity type
RBM-PMV0362E
RBM-PMV0902E
Allowable length of refrigerant piping
2 m to 10 m
PMV Kit
Refrigerant pipe
Label
Model name
Indoor unit capacity type
RBM-PMV0362E
RBM-PMV0902E
When connecting ø9.5 refrigerant pipes, be sure to insert a seal pipe between PMV main unit and the joint.
If the seal pipe is not inserted, refrigerant leakage is caused.
PMV Kit
Seal pipe
Diameter of refrigerant pipe
005 to 014 type
015 to 018 type
020 to 027 type
Indoor unit
Diameter of refrigerant pipe
005 to 014 type
015 to 018 type
020 to 027 type
Attached joint
ø6.4
ø6.4
ø9.5
NO GOOD
PMV Kit
Indoor unit
Note)
Do not connect two or more indoor units to one PMV Kit.
Arrange one indoor unit and one PMV Kit set to 1 by 1.
• Connecting direction of refrigerant pipe
When connecting pipes, be careful of direction of the
main unit. Be sure to install the main unit so that
[
] mark in the label directs upward.
For connection of the refrigerant pipes, follow the
arrow mark in the label and connect pipes after
confirming directions of indoor unit and outdoor unit.
Piping material and dimensions
ø6.4
ø6.4
ø9.5
CAUTION
44
OK
Indoor unit
Notes
Attached joint
Attached joint
Attached joint
Liquid pipe
PMV Kit