Equipment selection procedure

2-2. Combination conditions for indoor unit and outdoor unit

Indoor unit can connect 80 % to 130 % of Outdoor unit capacity.
2-2-1. For indoor unit, the capacity code is decided for each capacity rank.
Capacity rank type
Capacity
Equivalent to
code
HP
NOTE:
Capacity rank : Correspondence to Btu/h. Capacity code : Correspondence to Horsepower.
*1 : Capacity code of 005 type is the same as 007 type.
2-2-2. For outdoor unit, maximum No. of connectable indoor units and total
capacity code of indoor units are decided.
Outdoor unit
MCY-MHP0404HT*
MCY-MHP0504HT*
MCY-MHP0604HT*
005(*1)
007
008
009
010
0.8
0.8
0.9
1.0
1.1
Capacity code of outdoor unit
4
5
6
012
014
015
017
018
1.25
1.5
1.7
1.85
2.0
No. of connectable indoor units
2 to 6
2 to 6
2 to 6
11
020
024
027
030
036
2.25
2.5
3.0
3.2
4.0
Total capacity code of indoor units
3.2 to 5.2
4.0 to 6.5
4.8 to 7.8
048
056
5.0