Cooling / Heating Capacity Characteristics - Toshiba MCY-MHP0404HT-E Engineering Data Book

Side blow vrf outdoor units
Hide thumbs Also See for MCY-MHP0404HT-E:
Table of Contents

Advertisement

2
Equipment selection procedure

2-3. Cooling / heating capacity characteristics

2-3-1. Correction charts for cooling capacity calculation
[1] Capacity correction value vs. indoor air wet bulb temperature
[2] Capacity correction value vs. outdoor air dry bulb temperature
[3] Capacity correction value vs. connecting pipe length and lift difference between indoor and
outdoor units
[4]* Correction of outdoor unit diversity
* : Coefficient to use for correction of outdoor unit capacity when total capacity of the indoor units are not equal to the outdoor unit
capacity.
Indoor air wet bulb temp. (°C)
1.2
1.1
1.0
0.9
0.8
-5
0
5
10 15 20 25 30 35 40
Outdoor air dry bulb temp. (°C)
Pipe length (Equivalent length) L [m]
Standard capacity ratio
Indoor units total capacity ratio (%)
12