Differentials are used to determine the maximum variation
from set point and have a range of 0 through 10. The
table below shows the effect of differentials on cooling
cycles with a set point of 45°.
NOTE: Air temperature does not reflect product
temperatures.
Differential
Cycle Start
0
46°
1
47°
2
48°
3
49°
4
50°
5
51°
The graph below shows a unit's cooling cycle over time
with various differentials.
Factory Default
Up
Down
Factory Default will restore all settings to their factory
default.
To access Factory Default
1. Use Down
to select "Factory Default".
2. Press Select
.
Cycle End
44°
43°
42°
41°
40°
39°
Select
RETURN TO MENU
FACTORY DEFAULT
RESTORE?
To restore settings to their factory default
1. Use Down
to select "Restore?" and press Select
2. "Restore?" will change to "Restoring..." while settings
are restored. When restoration is complete,
"Restoring..." will return to "Restore".
To exit Factory Default use Up
Menu" and press Select
Re-Select Model
Up
Down
NOTICE
Before altering model selection, U-Line customer
service must be notified. Failure to notify
customer service will result in voiding of the
manufacturer warranty. Call U-Line Customer
Service for assistance.
Re-Select Model allows the unit's model configuration to
be modified. Changing the unit's model completely
reprograms available zones, relay assignments, dc output
assignments, etc.
To access Re-Select Model
1. Use Down
to select "Re-Select Model".
2. Press Select
.
To alter model setting
1. Use Down
to select "Model=" and press Select
"Model" will begin to flash.
u-line.com
to select "Return to
to confirm.
Select
RETURN TO MENU
RE-SELECT MODEL #
3018R
Service Mode 6
.
.