GOLD CGt Gas-Fired Water Boiler — Boiler Manual
3d
Venting — direct exhaust — vent starter
1. Select a vent pipe manufacturer and
obtain all vent components needed,
based on boiler location and venting
method.
. You must use the vent starter made
by the vent pipe manufacturer. See
Table 4, page 15, Vent system compo-
nents, for part number of each com-
ponent, listed by vent manufacturer.
Use only the vent
starter of the same
manufacturer as the
vent components. Do
not mix components
from different systems.
The vent system could
fail, causing flue gas
spillage, resulting in
severe personal injury
or death.
3. Follow all applicable national, state,
local or provincial codes when venting
the CGt boiler.
4. Connect vent starter to blower hous-
ing outlet as shown in the Figures 8
through 11, right.
a. Do not mix components from
different vent manufacturers.
b. Maintain minimum " clearance
from combustible materials to
vent pipe.
c. Seal with sealant specified by
vent pipe manufacturer, using ³⁄₈"
bead (not required for FasN-
Seal™).
d. Tighten strap at band clamp
screw until strap is snug around
blower housing.
16
Figure 8 FasNSeal™ vent starter
Figure 10 Saf-T Vent® vent starter
Figure 9 Z-Vent II vent starter
Figure 11 StaR-34 vent starter
Part Number 550-110-290/0107