T8200-TB20-9JS0/9JR0、T8200-TF20-9JS0/9JR0、T8200-TB21-9JS0/R0 Series Touch Screen Fan Coil Thermostat - Installation Instructions
T8200-TB20-9JS0/9JR0、T8200-TF20-9JS0/9JR0、T8200-TB21-9JS0/R0系列触摸屏风机盘管温控器 - 安装说明
使用说明
开关机设置: 按" "键一次开机;再按一次关机,同时关闭风机盘管、电动
阀。
模式调节: 开机状态下,按" M "键进行工作模式切换。液晶显示" "表示
制冷,显示" "表示制热,显示"
9JS0/9JR0中,当自动模式有效时," M "键失效,无通风模式,当设定温度
比测量温度高1℃以上时,自动进入制热模式,当设定温度比测量温度低1℃
以上时,自动进入制冷模式)
温度设置: 在开机状态下,按" ∧ "或" ∨ "可进行设置温度的调节,每按
一次,温度变化0.5℃。
风速调节:
制冷、制热模式下操作
温控器有4种风机速度,自动"
低"
"风速。按"
"按钮,将循环显示。
仅风机操作
温控器有3种风机速度,高"
速。按"
"按钮,将循环显示。
注意: 每一次开关T8000系列温控器,开始时都将启动低速风机。这一软启
动特点防止了高启动电流,同时节约了用电,3秒以后,风机按设定运转。
时钟和定时开关机设置:
时钟调整: 按" "键,直至出现" hh:mm "的" mm "闪烁,按" ∧ "或
" ∨ "键调整分钟。再按" "键," hh:mm "的" hh "闪烁,按" ∧ "
或" ∨ "键调整小时。再按"
" ∨ "键调整星期。
定时开关机设置: 开机状态下,按" "键,直至出现" hh:mm "、" "、
" ON "符号,并且" "、" ON "闪烁,按" ∧ "或" ∨ "键调整,每按
一次变化30分钟。再按" "键,直至出现" "、" OFF "符号闪烁,用
上述方法,设置定时关机的时间。设定一次定时开关机时间只能执行一次,
即只在一天内有效。
取消定时开关机设置: 开机状态下,按"
" "、" ON "符号,并且" "、" ON "闪烁,按" ∧ "或" ∨ "键调整
定时开机的时间调至" 00:00 ";再按" "键,直至出现" "、" OFF "
符号闪烁,用上述方法,将定时关机的时间调整为" 00:00 "。
按键锁功能:
锁按键功能: 如果温控器开启了锁按键功能,在没有人使用的情况下30秒后
会自动把按键锁上,禁止其他人员对温控器进行操作。
按键解锁: 按风速按键5秒即可解锁(在没有人使用的情况下30秒后会自动把
按键锁上)。
门卡功能 (T8200-TB20-9JS0/ T8200-TF20-9JS0/T8200-TB21-9JS0)
如安装了有人/无人监控装置,有人/无人模式"
进入有人/无人模式。
在T8200-TB20-9JS0和T8200-TB21-9JS0型号中,当门卡拔出后,进入无人
模式,此时液晶显示"
",如果温控器处于制冷模式时,温度自动设置为
26℃,风机低速运行。如果温控器处于制热模式时,温度自动设置为18℃,
风机低速运行。此时上下键调节温度功能失效。插入门卡后,恢复正常。
在T8200-TF20-9JS0型号中,手动模式下,当门卡拔出后,如果温控器处于制
冷模式时,温度自动设置为26℃,风机低速运行。如果温控器处于制热模式
时,温度自动设置为18℃,风机低速运行。自动模式下,当门卡拔出后,如
果室内温度大于26℃,温控器自动变成制冷模式并且冷水阀打开,风机低速
运行;当室温小于18℃,温控器自动变成制热模式并且热水阀打开,风机低
速运行;在18℃~26℃之间,冷水阀和热水阀关闭,风机低速运行。
外接温度传感器 (T8200-TB20-9JR0/ T8200-TF20-9JR0/T8200-TB21-9JR0):
当温控器接上外置传感器时,内置NTC自动失效。
计时功能:
在开机状态下,长按" "键5S,此时进入计时界面,此时显示的时间为温
控器累计运行的时间。
在关机状态下,长按" "键10S,进入计时界面,此时按"
计时间清零。
602Q-B01A-NB-Issue Date 12 2013
"表示通风。(注:在T8200-TF20-
"、高"
"、中"
"、中"
"、低"
"键,星期的显示符闪烁,按" ∧ "或
"键,直至出现" hh:mm "、
"将会启动。可通过门卡
"键可以将累
Instructions
On/Off Setting: Press " " to turn on, press again to turn off, close the fan and valve.
Mode Selection: Press " M " to change the working mode, " " for Cooling, " " for
" for venting. (For model T8200-TF20-9JS0/9JR0, key " M " is unavailable
Heating, "
under auto mode. When setting temperature is more than 1℃ higher than indoor
temperature, the mode will change to heating automatically, When setting
temperature is more than 1℃ lower than indoor temperature, the mode will change
to cooling automatically.)
Temperature Setting: Press either " ∧ " or " ∨ " button to increase or decrease by 0.5℃.
Fan Speed Adjustment:
Cooling or Heating Mode Operation
T8000, has 4 speeds fan control: Auto "
Low "
" fan. Short press the "
"、
Fan only Operation
T8000, has 3 speeds fan control; High "
"
" fan. Short press the "
"风
Note: Fan stops at Floor Heating Mode.
Time Adjustment and Time-On/Off Operation:
Time Adjustment: Continuously press " " button until " mm " in " hh:mm " blinks,
then press " ∧ " or " ∨ " to adjust the minute. Press " " button again until " hh " in
" hh:mm " blinks, then press " ∧ " or " ∨ " to adjust the hour. Press " " button again
and adjust the weekday by the same method.
Time-On/Off Operation: Continuously press " " button until the '' hh:mm '', " ",
" ON " appear, and " ", " ON " blink. Press either " ∧ " or " ∨ " key to adjust the Time-On
by 30 minutes. Press " " button again until " ", " OFF " blink. Then adjust the Time-
Off by the same method. Time-On/Off setting performs only once within one day.
Time-On/Off Cancel: Continuously press " " button until the '' hh:mm '', " ",
" ON " appear, and " ", " ON " blink. Press either " ∧ " or " ∨ " key to adjust the Time-
On '' 00:00 ''. Press " " button again until " ", " OFF " blink. Then adjust the Time-
Off '' 00:00 '' by the same method.
Lock function:
Lock function: If Lock function is enabled, the thermostat will be locked
automatically after 30 seconds unused.
Unlock function: Hold down the fan key 5 seconds to unlock.
Unoccupied mode (T8200-TB20-9JS0/ T8200-TF20-9JS0/T8200-TB21-9JS0):
Occupied/Unoccupied mode "
by entrance card.
To T8200-TB20-9JS0 and T8200-TB21-9JS0: While entrance card is pulled out,
the temperature automatically set to 26℃, fan is on LO-speed if the thermostat
is in cool mode; the temperature set to 18℃, fan is on LO-speed if in heat mode.
Temperature Setting is invalid until the entrance card is inserted again.
To T8200-TF20-9JS0: In Manual mode, while entrance card is pulled out, the
temperature automatically set to 26℃, fan is on LO-speed if the thermostat is in
cool mode; the temperature set to 18℃, fan is on LO-speed if in heat mode. In
Auto mode, while entrance card is pulled out, if the room temperature is over 26℃,
the thermostat becomes cooling mode automatically, cold water valve is opened
and fan is on LO-speed; if the room temperature is below 18℃, the thermostat
becomes heating mode automatically, hot water valve is opened and fan is on LO-
speed; If the room temperature is between 18℃ to 26℃, both cold and hot water
valve are closed, and fan is on LO-speed.
Remote Temperature sensor (T8200-TB20-9JR0/ T8200-TF20-9JR0/T8200-
TB21-9JR0):
When remote sensor is connected, the built-in sensor will be disable.
Timer Function:
On power on status, hold the " " button for 5s to enter the Timer interface, where
the thermostat's accumulated running time is showing.
On power off status, hold the " " button for 10s to enter the Timer interface,
accumulated running time can be cleared by pressing "
", High "
", Middle "
" button switches through the sequence.
", Middle "
", Low
"button switches through the sequence.
" is active if monitor is equipped, which is operated
".
",
3

Advertisement

loading

This manual is also suitable for:

T8200-tf20-9js0/9jr0 seriesT8200-tb21-9js0/r0 series