LG AS-W096E1G0 Engineering Product Data Book page 78

Hide thumbs Also See for AS-W096E1G0:
Table of Contents

Advertisement

9. Capacity coefficient factor
Model No.
AS-W096ADR0
AS-W0964GG1
AS-W096E*H2
AS-W096E1G0
AS-W096F*G2
AS-W096F1G2
AS-W096U*H1
AS-W126ADR0
AS-W1264GG1
AS-W126E*H2
AS-W126E1G0
AS-W126F*G2
AS-W126F1G2
AS-W126U*H1
AS-W1863*H3
AS-W1865DH2
AS-W1865GG1
AS-W1868*H1
AS-W2463*H3
AS-W2465DH2
AS-W2468*H1
AS-W306DGM0
AS-W366DGM0
Indoor unit
A
B
Outdoor unit
Notes
❈ Equivalent pipe length = actual pipe length + number of band x 0.3
❈ Additional Refrigerant Charge
Example: For Model No. AS-W126ADR0 having 15m pipe length, additional refrigerant to be charged is
(15-7) x 20 = 160g
* Refer to the specification for the maximum pipe length of each model.
* 18k S5/S8 Chassis total piping length is 15m.
Max. Pipe
Length(m)
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
30
30
30
50
50
Outdoor unit
A
Indoor unit
B
Max. Elevation
(m)
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
15
15
15
30
30
Outdoor unit
A
Oil trap
Indoor unit
B
If piping length is more than 5m
Additional
Refrigerant[g/m(oz/ft)]
20(0.22)
20(0.22)
20(0.22)
20(0.22)
20(0.22)
20(0.22)
20(0.22)
20(0.22)
20(0.22)
20(0.22)
20(0.22)
20(0.22)
20(0.22)
20(0.22)
20(0.22)
20(0.22)
20(0.22)
20(0.22)
30(0.32)
30(0.32)
30(0.32)
30(0.32)
35(0.37)
CAUTION:
• Capacity is based on
standard length and
maximum allowance
length is on the basis
of reliability.
• Oil trap should be
installed every 5~7
meters.
2008 Product Data
77